Siemens SENTRON ATC6500 Manual page 130

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

Connection
7.6 Connection of 3WL air circuit breakers, FS I - III
Note
Implementation of the power supply
More information on implementing the power supply of the ATC6500 via the inputs 53, 54
and / or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).
Note
Mechanical interlock
A mechanical interlock of the circuit breakers can be applied in addition.
Note
Expansion modules
For additional functions, expansion modules with inputs/outputs can be attached if necessary
(see chapter Expansion modules (Page 209)).
You can find more information on the technical specifications of the circuit breaker in the
Operating Instructions of the 3WL air circuit breaker
(https://support.industry.siemens.com/cs/ww/en/view/8912465).
Terminal
Parameter code
-
P02.01 System configuration
-
P02.22 Management of the tie breaker
(TB)
-
P08.01 Type of breaker
40 (INP1)
P12.1.01 Function of the input INP1
41 (INP2)
P12.2.01 Function of the input INP2
42 (INP3)
P12.3.01 Function of the input INP3
43 (INP4)
P12.4.01 Function of the input INP4
55 (OUT1)
P13.1.01 Function of the output OUT1
57 (OUT2)
P13.2.01 Function of the output OUT2
58 (OUT3)
P13.3.01 Function of the output OUT3
60 (OUT4)
P13.4.01 Function of the output OUT4
128
Settings
A: 2S-0T
OFF
Breaker pulse or breaker continuous
Source 1 breaker closed (feedback 1)
Source 2 breaker closed (feedback 2)
Source 1 breaker protection (Trip 1)
Source 2 breaker protection (Trip 2)
Open Source 1 breaker
Close Source 1 breaker
Open Source 2 breaker
Close Source 2 breaker
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01

Advertisement

Table of Contents
loading

Table of Contents