Keys; Interface - Siemens SENTRON ATC6500 Manual

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

See also
Parameters (Page 160)
4.2

Keys

No.
Key
Function
1
<<
Using this key in the manual mode, it is possible to toggle between the switching devices
2
>>
Using this key in the manual mode, it is possible to toggle between the switching devices
4
TEST
Pressing the TEST key for more than 0.5 seconds selects the TEST mode. The key must subse-
quently be held down for 5 seconds to start the TEST.
6
AUT
Pressing the AUT key for more than 0.5 seconds selects the automatic mode.
8
MAN
Pressing the MAN key for more than 0.5 seconds selects the manual mode.
10
OFF
Pressing the OFF key for more than 0.5 seconds selects the OFF mode. In addition, individual menus
can be closed by briefly pressing the OFF key.
14
CLOSE
Using this key in the manual mode, it is possible to close the selected switching device
17
OPEN
Using this key in the manual mode, it is possible to open the selected switching device
20
Pressing this key switches between menu pages in the main menu. It is also used for incrementing
the parameters.
21
Pressing this key switches between menu pages in the main menu. In addition, it switches between
the parameters in the setup mode.
22
Pressing the ✓ key opens the main menu. This key is also used for selecting and confirming settings.
23
Pressing this key switches between menu pages. In addition, it switches between the parameters in
the setup menu.
24
Pressing this key switches between menu pages. It is also used for reducing the parameters.
4.3

Interface

A 3KC9000-8TL73 USB front interface can be attached to interface 11. This enables the
ATC6500 transfer control device to be parameterized from the front using powerconfig
(Version 3.12 or higher).
Further information on the 3KC9000-8TL73 USB front interface can be found in chapter
Parameterization via the front interface (Page 159) or in chapter USB front interface -
3KC9000-8TL73 (Page 225).
QR code
QR code 12 contains information that refers to the Industry Mall page of the ATC6500
transfer control device. where further information is available, e.g. operating instructions and
certificates.
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Product description
4.2 Keys
35

Advertisement

Table of Contents
loading