Code Command
C18
Reset alarms A03 - A04
C19
Simulates priority source fail-
ure
5.1.9.3

Event log

In the event log of the ATC6500 you can view the last 250 events. The event log is accessed
by:
● Selection of the Event Log symbol
● Scrolling through the display pages
The event log shows:
● Number of the event
● Error code
● Date / time and a brief description of the event
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Designation on the
Required
ATC
password
RESET A03/04
Advanced Restores the opening or closing command of
FAIL.SIMULATION
Advanced The device switches to test mode and simu-
Description
the switching devices after generating the
alarms A03 - A04
lates failure of the priority source for two
minutes.
After this, it executes a load transfer as pro-
grammed (see chapter Simulation of priority
source failure (Page 69)).
Functions
5.1 Basic functions