Transfer With Contactors - Siemens SENTRON ATC6500 Manual

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

Connection
7.2 General connection drawings
7.2.4

Transfer with contactors

Code
BRK1 / BRK2
F1 / F2
Note
Implementation of the power supply
More information on implementing the power supply of the ATC6500 via the inputs 53, 54
and / or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).
As shown above, when switching between contactors, the following basic parameters must
be set:
Terminal
Parameter code
-
P02.01 System configuration
-
P02.22 Management of the tie breaker
(TB)
-
P08.01 Type of breaker
40 (INP1)
P12.1.01 Function of the input INP1
41 (INP2)
P12.2.01 Function of the input INP2
57 (OUT2)
P13.1.01 Function of the output OUT1
60 (OUT4)
P13.2.01 Function of the output OUT2
94
Description
Breaker 1 / 2
Source fuse
Mechanical interlock
Settings
A: 2S-0T
OFF
Contactors
Source 1 breaker closed (feedback 1)
Source 2 breaker closed (feedback 2)
Close Source 1 contactor
Close Source 2 contactor
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01