Commands (Use With Modbus Function 06) - Siemens SENTRON ATC6500 Manual

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

10.4.3

Commands (use with MODBUS function 06)

Address
4F00H
4F01H
4F02H
4F03H
4F04H
4F05H
4F06H
4F07H
2F00H
2F0AH
2F03H
2F07H
2FF0H
28FAH
Remote variables
If you write AAh in the corresponding address, the remote variable is set to 1. If you enter
BBh, the remote variable is set to 0 and disabled accordingly.
Changing the operating mode
The following values must be sent to the address 2F00H in order to set the corresponding
operating mode:
Bit
0
1
2
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Words
Function
1
Enable remote variable 1
1
Enable remote variable 2
1
Enable remote variable 3
1
Enable remote variable 4
1
Enable remote variable 5
1
Enable remote variable 6
1
Enable remote variable 7
1
Enable remote variable 8
1
Change of operating mode
1
Simulation of pressing a key on the user interface
1
Value 01h: Memory in EEPROM
Value 04h: Reboot
1
Value 00h: Reset ATC6500
Value 01h: Reset the ATC6500 and save in FRAM
1
Execution of the Commands menu
1
Value 01h: Save the setting of the real-time clock
Meaning
Enable OFF mode
Enable MAN mode
Enable AUT mode
MODBUS communication
10.4 Data library
199