Relay outputs OUT7, OUT9, OUT10: Terminals 19-21, 30-32, 33-35
Contact type
Rated contact current
UL Rating
Output voltage (maximum)
Mechanical/electrical endurance (cycle)
Insulation voltage U
i
Impulse withstand voltage U
Power frequency withstand voltage OUT7, OUT9,
OUT10
Ambient conditions
Operating temperature
Storage temperature
Relative humidity
Maximum degree of pollution
Overvoltage category
Measuring category
Connections
Connecting terminals
Cable cross-section (min-max)
Cable cross-section (min-max) acc. to UL 508
Tightening torque
Enclosure
Enclosure material
Version
Degree of protection
Weight
Certifications and approvals
The following standards are complied with:
Complies with standards
UL marking
Note: This product is designed for environment A. Its use in a Class B environment can lead to unwanted electromagnetic
problems. Consideration should be given to possible measures for mitigating the electromagnetic radiation.
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
OUT7, OUT9, OUT10 7.3 kV
imp
3 x 1 CO contact
AC1 8A 250V
AC15 1.5A 250V
DC1 8A 30V
B300
30 VDC 1 A auxiliary duty
250 VAC
1x10^7 / 1x10^5
250 VAC
3 kV
-30 ...+70 °C
-30 ...+80 °C
<80 % (IEC / EN 60068-2-78)
2
3
CAT III
Removable / plug-in
0.2 ...2.5 mm2 (AWG 24 ... 12)
0.75 ...2.5 mm2 (AWG 18 ... 12)
0.56 Nm (5 lbf in)
Polycarbonate
Door installation
IP40 at front (can be increased to IP65 by using IP protective seal),
IP20 at rear
680 g
EAC, cULus
IEC / EN 61010-1, IEC / EN 61010-2,
IEC / EN 61000-6-3, IEC / EN 61000-6-4,
UL508, CSA C22.2-N°14
Use 60°C/75°C copper (CU) conductor only
AWG Range: 18 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque:
4.5lb.in
Flat panel mounting on a Type 1 or 4X enclosure