Siemens SENTRON ATC6500 Manual page 102

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

Connection
7.2 General connection drawings
Terminal
Parameter code
-
P02.01 System configuration
-
P02.22 Management of the tie breaker (TB)
-
P08.01 Type of breaker
40 (INP1)
P12.1.01 Function of the input INP1
41 (INP2)
P12.2.01 Function of the input INP2
42 (INP3)
P12.3.01 Function of the input INP3
43 (INP4)
P12.4.01 Function of the input INP4
44 (INP5)
P12.05.01 Function of the input INP5
45 (INP6)
P12.06.01 Function of the input INP6
55 (OUT1)
P13.1.01 Function of the output OUT1
57 (OUT2)
P13.2.01 Function of the output OUT2
58 (OUT3)
P13.3.01 Function of the output OUT3
60 (OUT4)
P13.4.01 Function of the output OUT4
20 (OUT7)
P13.7.01 Function of the output OUT7
31 (OUT9)
P13.9.01 Function of the output OUT9
100
Settings
2S – 1T – SI or 2S – 1T - AI
Breaker pulse or breaker continuous
Breaker pulse or breaker continuous
Source 1 breaker closed (feedback 1)
Source 2 breaker closed (feedback 2)
Tie breaker TB / NPL closed (feedback message)
Source 1 breaker protection (Trip 1)
Source 2 breaker protection (Trip 2)
Tie breaker protection (Trip)
Open Source 1 breaker
Close Source 1 breaker
Open Source 2 breaker
Close Source 2 breaker
Open tie breaker TB / NPL
Close tie breaker TB / NPL
Manual, 05/2019, L1V30538268002A-01
3KC ATC6500 transfer control device