Connection
7.7 Connection of 3WT8 air circuit breakers
Note
Implementation of the power supply
More information on implementing the power supply of the ATC6500 via the inputs 53, 54
and / or the inputs 26, 27 can be found in chapter Connection of the power supply (Page 83).
Note
Mechanical / electrical interlocks
The two breakers of the infeed sources are electrically interlocked in the circuit diagram
shown above. The tie breaker is not interlocked. An additional mechanical interlock can be
applied for the two breakers BRK1, BRK2.
Note
Expansion modules
For additional functions, expansion modules with inputs/outputs can be attached if necessary
(see chapter Expansion modules (Page 209)).
You can find more information on the technical specifications of the circuit breaker in the
Operating Manual of the SENTRON 3WT8 air circuit breaker
(https://support.industry.siemens.com/cs/ww/en/view/33272206).
Terminal
Parameter code
-
P02.01 System configuration
-
P02.22 Management of the tie breaker (TB)
-
P08.01 Type of breaker
40 (INP1)
P12.1.01 Function of the input INP1
41 (INP2)
P12.2.01 Function of the input INP2
42 (INP3)
P12.3.01 Function of the input INP3
43 (INP4)
P12.4.01 Function of the input INP4
44 (INP5)
P12.05.01 Function of the input INP5
45 (INP6)
P12.06.01 Function of the input INP6
55 (OUT1)
P13.1.01 Function of the output OUT1
57 (OUT2)
P13.2.01 Function of the output OUT2
58 (OUT3)
P13.3.01 Function of the output OUT3
60 (OUT4)
P13.4.01 Function of the output OUT4
14 (OUT12) P13.12.01 Function of the output OUT12
24 (OUT13) P13.13.01 Function of the output OUT13
136
Settings
2S–1T–PL or 2S–NPL
Breaker pulse or breaker continuous
Breaker pulse or breaker continuous
Source 1 breaker closed (feedback 1)
Source 2 breaker closed (feedback 2)
Source 1 breaker protection (Trip 1)
Source 2 breaker protection (Trip 2)
Tie breaker TB / NPL closed (feedback message)
Tie breaker TB / NPL protection (Trip)
Open Source 1 breaker
Close Source 1 breaker
Open Source 2 breaker
Close Source 2 breaker
Open tie breaker TB / NPL
Close tie breaker TB / NPL