12.2

Transfer sequence

12.2.1

Transfer sequence for application A: 2S - 0T

If Source 1 is regarded as the priority source, a transfer to the alternative source (Source 2)
takes place and an automatic return to the priority source according to the diagram below:
Note
• In addition to the various delay times for limit violation, the transfer is also influenced by
the interlock times under parameter P07.n.02.
• An automatic return can be prevented by parameter P08.04 or a digital input.
See also
Application A: 2S – 0T (Page 21)
Parameters (Page 160)
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Transfer
12.2 Transfer sequence
229