8.2 Inputs and outputs of the ATC6500
Some functions require another numeric parameter. This is specified by parameters by
means of an index.
Note
Use of an index
An index is used if additional functions are to be used as a source for the output.
For example, an output can function as a source for a counter or for a user alarm.
On replacement or subsequent modification of the modules, attention must be paid to the
addressing (see chapter Addressing of the expansion modules with digital inputs/outputs
(Page 152)).
8.2.5

Table of functions of the digital outputs

The table below lists all functions that can be assigned to the programmable digital outputs
OUTx.
Function
Disabled
Configurable
Close Source 1 contactor/breaker L1 close
Open Source 1 contactor/breaker L1 open
Close Source 2 contactor/breaker L2 close
Open Source 2 contactor/breaker L2 open
Open Source 1 and Source 2
Undervoltage release breaker 1
Undervoltage release breaker 2
Control Generator 1
Control Generator 2
ATC ready
Global alarm A
Global alarm B
Source 1 voltage status
Source 2 status
150
Designation on the ATC6500
Disabled
Configurable
L1-L2 open
Min V coil 1
Min V coil 2
Start generator 1
Start generator 2
ATC ready
Global alarm A
Global alarm B
SRC1 VOLTAGE OK
SRC2 VOLTAGE OK
Description
Output disabled
Free configuration by the user.
Command to close the contactor/breaker of Source 1.
Command to open the breaker of Source 1 with possi-
ble spring load.
Command to close the contactor/breaker of Source 2.
Command to open the breaker of Source 2 with possi-
ble spring load.
Open both breakers / neutral position of the transfer
switching equipment with motor operator.
Controls the undervoltage release by opening break-
er 1 before the spring load cycle.
Controls the undervoltage release by opening break-
er 2 before the spring load cycle.
Control of the Start / Stop remote control of the gen-
erator on Source 1.
Control of the Start / Stop remote control of the gen-
erator on Source 2.
ATC in automatic mode, without alarms, ready to
switch.
Output enabled in the presence of any alarm with the
property "Global alarm A"
Output enabled in the presence of any alarm with the
property "Global alarm B"
This output is enabled if all conditions for the connec-
tion of the load to Source 1 have been met.
This output is enabled if all conditions for the connec-
tion of the load to Source 2 have been met.
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01