P06 - Source Lines - Siemens SENTRON ATC6500 Manual

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

Parameterization
9.4 Parameters
9.4.6

P06 - Source Lines

This menu is divided into 2 sections for Source 1 (SRC1; SRC1 = Source 1) and Source 2
(SRC2).
P06
Designation on ATC
Qn, n = 1...2)
display
P06.n.01
SOURCE
DESCRIPTION
P06.n.02
PRIORITY
P06.n.03
SOURCE TYPE
P06.n.04
COOLING TIME
168
Description
Description of source
- This parameter enables the user to de-
fine any name for the sources.
This name then appears on the Overview
display page.
Priority source
- This parameter defines priority of the
source. If both sources should be availa-
ble, the source with priority 1 is regarded
as the priority source. If both sources
should have the same priority, Source 1 is
prioritized.
Type of source
- This parameter defines whether the con-
nected source is a generator or a network.
The corresponding diagram is then shown
on the Overview display page.
Generator cooling time
– Maximum duration of the cooling cycle.
Time that elapses between the disconnec-
tion of load from the generator and the
engine actually stopping.
Note: If P06.n.03 is set to generator.
Unit
Default
Range
Qn
(char*6)
n
1/2
Network
Network
Generator
sec
120
1-3600
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01