Siemens SENTRON ATC6500 Manual page 202

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

MODBUS communication
10.4 Data library
Key press simulation
The following values must be sent to the address 2F0AH in order to simulate the
corresponding key press:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
Execution of the Commands menu
The following values between 0 and 15 must be sent to the address 2FF0H in order to
execute the corresponding command:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
200
Meaning
▲ key
Key MAN
► key
<< key
Key TEST
AUT key
Key OFF
OPEN key
>> key
▼ key
✓ key
◄ key
CLOSE key
Meaning
Reset maintenance 1
Reset maintenance 2
Reset maintenance operations 1
Reset maintenance operations 2
Reset counter CNTx
Reset status limit threshold LIMx
Reset hours counter Source 1
Reset hours counter Source 2
Reset hours counter Breaker 1
Reset hours counter Breaker 2
Reset breaker operation
Reset event log
Restore default parameters
Save parameters in backup memory
Reload parameters from backup memory
Forced changeover I / O
Reset A03 - A04 alarms
Simulates priority source failure
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01