MODBUS communication
10.4 Data library
③
Key press simulation
The following values must be sent to the address 2F0AH in order to simulate the
corresponding key press:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
④
Execution of the Commands menu
The following values between 0 and 15 must be sent to the address 2FF0H in order to
execute the corresponding command:
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
200
Meaning
▲ key
Key MAN
► key
<< key
Key TEST
AUT key
Key OFF
OPEN key
>> key
▼ key
✓ key
◄ key
CLOSE key
Meaning
Reset maintenance 1
Reset maintenance 2
Reset maintenance operations 1
Reset maintenance operations 2
Reset counter CNTx
Reset status limit threshold LIMx
Reset hours counter Source 1
Reset hours counter Source 2
Reset hours counter Breaker 1
Reset hours counter Breaker 2
Reset breaker operation
Reset event log
Restore default parameters
Save parameters in backup memory
Reload parameters from backup memory
Forced changeover I / O
Reset A03 - A04 alarms
Simulates priority source failure
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01