Switching On Test Mode - Siemens FS20 Commissioning, Maintenance, Troubleshooting

Fire detection system
Hide thumbs Also See for FS20:
Table of Contents

Advertisement

21.20 Switching on test mode

Building Technologies
Fire Safety
1. Select 'Topology' > ↑ 'Detection tree' in the main menu.
2. Select the element you want to switch to test mode: 'Area', 'Section', or 'Zone'
3. Press the 'More Options' softkey and select 'Execute commands'.
4. Select a command from the following table.
 The yellow 'DETECTOR TEST' LED lights up.
 The element is in test mode.
Element
Area
↑ Section
Zone
Detailed commissioning steps
Switching on test mode
Command
'Non-MCP zones det.test'
'MCP zones det.test'
'Non-MCP zones det.test'
'MCP zones det.test'
'Detector test'
21
89 | 188
009052_s_en_--
2016-06-02