Updating the firmware
29

Station: Updating the FW of the additional CPUs only

29.2.5.5 Error during firmware update
29.3 Station: Updating the FW of the additional CPUs

29.3.1 Standalone station and SAFEDLINK station

132 | 188
Building Technologies
Fire Safety
If errors occur during the firmware update, the error messages are shown after the
update on the 'Station' display. The line 'Press Silence buzzer button' is displayed
after the error messages.
1. Press <Silence buzzer> on the Person Machine Interface.
 The 'Station' restarts.
 After a few minutes, the 'Buzzer' sounds twice.
2. Press <Acknowledge> on the Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.
Updating additional CPUs at the 'Station'
If errors are present for additional CPUs following the firmware update, you can
perform the update for the additional CPUs again at the 'Station'.
1. In the 'Main menu', select the 'Topology' > 'Hardware tree' > 'Station' menu
item.
2. Press <More Options>.
3. Select 'Execute commands'.
 The 'Select command' window is displayed.
4. Select 'Update incompatible firmware'.
 The firmware of the additional CPUs is updated.
only
If the ↑ 'Station' firmware is up to date and components have been changed, then it
is only necessary to update the additional ↑ CPUs. The procedure for updating the
firmware depends on the 'Station' function. The procedures are described in the
following chapters.
You will find additional information about the individual steps on the specified
pages.
ϖ Familiarize yourself with the information in 'Preparation and security [➙ 117]'.
1. Connect the PC to the ↑ 'Station'. Link [➙ 27]
2. Enable the 'Station'.
Press <MENU> and enter a valid PIN.
3. Update the firmware of the additional CPUs if there is a higher firmware version
status. Select the local connection as the connection type. Link [➙ 134]
4. Disconnect the PC from the 'Station'. Link [➙ 27]
See also
1 Loading configuration from the station to the PC [➙ 32]
009052_s_en_--
2016-06-02