Advertisement

FXS901
User Manual
Smart Infrastructure
A6V10336897_d_en_
2019-12-10

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FXS901

  • Page 1 FXS901 User Manual Smart Infrastructure A6V10336897_d_en_ 2019-12-10...
  • Page 2: Table Of Contents

    5.27 HOW TO UPLOAD LOG FILE ..........................44 5.28 HOW TO CHANGE LANGUAGE ........................45 5.29 HOW TO BACKUP PANEL ..........................46 5.30 HOW TO RESTORE PANEL..........................47 5.31 HOW TO CONFIG THE PROGRAM KEY ......................48 5.32 HOW TO VIEW THE VERSION OF FXS901 ......................49 A6V10336897_d_en_ 1/49...
  • Page 3: Introduction

    FXS901 software is mainly used for the engineering commissioning and maintenance of the FC901/FC2005 fire alarm system. Two versions of the software are available for the different channels, FXS901-U2 for the Desigo version and FXS901-U3 for the Cerberus Pro version.
  • Page 4 FXS901 User Manual 3. Click “Next” > “Next” to confirm the installation and then the installation starts. 4. During the tool installation process, the device driver installation wizard pops up automatically. Click “Next” to continue installing the driver. A6V10336897_d_en_ 3/49...
  • Page 5 5. If Windows security pops up, select “Install this driver software anyway” to continue. 4/49 A6V10336897_d_en_...
  • Page 6 FXS901 User Manual 6. Wait until you see the below screen, then click “Finish” to finish the driver installation. 7. Wait until you see the below screen, then click “Close” to finish the tool installation. A6V10336897_d_en_ 5/49...
  • Page 7: Usb Driver

    USB DRIVER The USB driver is installed automatically while installing the tool. If the automatic installation fails, the below error message pops up when using the tool: In this case, uses can install the usb driver manually: Step 1: Insert the USB cable, then the following window “Found New Hardware Wizard” pops up automatically.
  • Page 8 FXS901 User Manual Step 3: Select the item “Search for the best driver in these location” and “Include this location in the search” for the FXS901 software (with driver) and click on "Next". A6V10336897_d_en_ 7/49...
  • Page 9: Uninstallation

    UNINSTALLATION There are two ways to uninstall the FXS901 software. The first way: Click the Windows icon > “All programs” > “SIEMENS FXS901-U3 Configuration Tool” > “Uninstall FXS901-U3”, then click "Yes" to uninstall or click "No" to cancel. The second way: Open the Control Panel and then the “Programs and Features”. Find “FXS901-U3 Configuration Tool”, and then click “Uninstall”.
  • Page 10: Start/Exit

    Click "OK" to save it and exit FXS901. The second way: Directly click on the “X” on the top right corner of the window. System will remind users to "save the file" if the document is changed. Click on "OK" to save it and exit FXS901. A6V10336897_d_en_...
  • Page 11: Interface

    INTERFACE DISPLAY OVERVIEW Detection Tree Dialer Group Hardware Tree Control Tree Children View Menu Bar Tool Bar Property View TOOL BAR OVERVIEW Create a new configuration file Synchronize FACP time Open an existing configuration file Export device list Save the current configuration file Copy Upload configure files (FACPžPC) Paste...
  • Page 12: Operation

    FXS901 User Manual OPERATION HOW TO SELECT THE PANEL TYPE Before creating a new configure file, users need to select the panel type that matches with the field application. Click “Edit” > “Panel Type” to select the panel type that matches with the field application.
  • Page 13: How To Create A New Configure File

    HOW TO CREATE A NEW CONFIGURE FILE Directly click on the icon “/” in the toolbar or click "File" > “New”. Input a name for the new file in the pop up window and click “Save”, then the configure file with default setting is displayed as below: Edit the parameters in the property view.
  • Page 14: How To Open A Configure File

    FXS901 User Manual HOW TO OPEN A CONFIGURE FILE Click “File” > “Open”. Select the configure file that you want to open and then click “Open”. A6V10336897_d_en_ 13/49...
  • Page 15: How To Add A Device

    HOW TO ADD A DEVICE 1. Under the Hardware Tree > Addressable Loop, right click “Line 1”, and then click “Insert Node”. All selectable device series are listed. 2. Click the wanted series, and then all selectable devices are listed. Click on the wanted device, select the zone type and then click “OK”.
  • Page 16: How To Add A Zone

    FXS901 User Manual HOW TO ADD A ZONE 1. Right click “New FACP1” (Default name of the controller) under the Detection tree, and then click “Insert Node”. All selectable zones are listed. Click on the wanted zone, and then the zone is added and listed under “New FACP1”...
  • Page 17: How To Add A Channel

    HOW TO ADD A CHANNEL 1. Right click a device under Line 1 and then click “Insert Node”. All selectable channels are listed. Select the wanted channel and click on it. Then the channel is added and displayed under the device and on the Children view.
  • Page 18: How To Add A Sounder (Audible) Base

    FXS901 User Manual HOW TO ADD A SOUNDER (AUDIBLE) BASE 1. Select a detector under Line 1, which is installed with sounder base, and then right click on it. Click “Insert Node” > “2 audible control functions”. Then the 2 channels sounder base is added and displayed under the device and on the Children view.
  • Page 19: How To Add A Printer

    HOW TO ADD A PRINTER 1. Right click “UFP Line” under UFP, and then click “Insert Node” > “Point UFP Printer”. The printer is added and displayed under the UFP line and on the Children view. 2. Select the printer and edit its parameters in the property view. The following parameters can be set: Supervision: Define the printer whether it is supervised.
  • Page 20: How To Add A Fsd (Annunciator)

    FXS901 User Manual HOW TO ADD A FSD (ANNUNCIATOR) 1. Right click “UFP Line” under UFP, and then click “Insert Node” > “Point UFP Annunciator”. The annunciator is added and displayed under the UFP line and on the Children view.
  • Page 21: How To Add A Led Annunciator

    5.10 HOW TO ADD A LED ANNUNCIATOR 1. Right click “UFP Line” under UFP, and then click “Insert Node”. Select the wanted LED annunciator and click on it. Then the LED annunciator is added and displayed under the UFP line and on the Children view. 2.
  • Page 22: How To Add Citytie Or Leaseline

    FXS901 User Manual 5.11 HOW TO ADD CITYTIE OR LEASELINE Only one of CityTie and LeaseLine can be connected to the control panel at the same time. Below is how to select between CityTie and LeaseLine under CTLL. 1. Click “CTLL” under the Hardware tree. In the property window, click the drop down list for “WorkMode”...
  • Page 23: How To Delete A Device/Zone/Channel

    5.12 HOW TO DELETE A DEVICE/ZONE/CHANNEL 1. Right click the device/zone/channel which you want to delete, and then click “Delete Node”. The device/zone/channel is deleted. 2. Save the configuration. 22/49 A6V10336897_d_en_...
  • Page 24: How To Edit Parameters

    FXS901 User Manual 5.13 HOW TO EDIT PARAMETERS Select a zone/device/channel, and then all editable parameters are displayed on the Property window. Edit these parameters and save the configuration. A6V10336897_d_en_ 23/49...
  • Page 25: How To Assign A Channel To Zone/Effect

    5.14 HOW TO ASSIGN A CHANNEL TO ZONE/EFFECT Input channel should be assigned to zone under detection tree. Output channel should be dragged to effect under control tree. For input channel 1. Right click an input channel from the hardware tree, and then click “Assign to Zone”. Select the target zone, and then the channel is added to the selected Zone under the Detection tree.
  • Page 26: How To Create A Control Logic

    FXS901 User Manual 5.15 HOW TO CREATE A CONTROL LOGIC FXS901 software provides 7 kinds of control logic: · Basic control · Advanced control · User control · LED control · Releasing control · Mimic control · Test control The table below shows the differences:...
  • Page 27 Control 2. The new control logic is now created. NOTE · FXS901 software provides an easy way to assign a device/zone to control tree from detection tree and hardware tree. Select one device/ zone and drag to control tree and release directly, the assignment is finished.
  • Page 28: How To Configure The Dialer Group

    FXS901 User Manual 5.16 HOW TO CONFIGURE THE DIALER GROUP 1. From the dialer group, right click “Dialer Group Config”, then click “Insert Node” > “DialerGroup”. A new dialer group is added and displayed under the Dialer Group Config. 2. Drag the wanted zone from the detection tree to the target dialer group.
  • Page 29: How To Synchronize Pad5 Nac With Nac Source

    5.17 HOW TO SYNCHRONIZE PAD5 NAC WITH NAC SOURCE A NAC connected to PAD5 can be configured to 4 different types: Conventional NAC, Synch Strobes Horns, Gated NAC Conventional and Gated NAC Synch Strobes Horns. The Conventional NAC and Synch Strobes Horns type NAC work according to PAD5 settings.
  • Page 30 FXS901 User Manual A6V10336897_d_en_ 29/49...
  • Page 31: How To Download/Upload Configure File

    5.18 HOW TO DOWNLOAD/UPLOAD CONFIGURE FILE Download configure file 1. When the configuration is finished on the tool, connect the communication cable between PC and FACP. 2. On the tool, click “Edit” > “Download Configure File (PC ž FACP)”. NOTE First time users may get an “Install New Hardware Wizard”...
  • Page 32 FXS901 User Manual Upload configure file: If there is a large amount of configurations that need to be modified, it is suggested to upload them to PC for easier modifying. 1. Connect the communication cable between PC and FACP. 2. On the tool, click "Edit" > "Upload Configure Files (FACPžPC)".
  • Page 33: How To Download Panel System File

    5.19 HOW TO DOWNLOAD PANEL SYSTEM FILE After a new panel is assembled, a panel firmware system file may need to be downloaded to the panel. 1. Connect the communication cable between PC and FACP. 2. Select "Download System File (PCž FACP)" from "Edit" menu. NOTE First time users may get an “Install New Hardware Wizard”...
  • Page 34 FXS901 User Manual NOTE ImgInfo is filled in by system and is not allowed to be edited. If the “Keep Engineering Data File” checkbox is enabled, the exiting configuration file on the panel will not be reset. Otherwise, the configuration file on panel will be reset to default.
  • Page 35: How To Download Fsd (Remote Annunciator) System File

    5.20 HOW TO DOWNLOAD FSD (REMOTE ANNUNCIATOR) SYSTEM FILE This function is used to download the system file from PC to FSD (remote annunciator). 1. Click "Edit" > "Download FSD System File". 2. Select communication port and click “Select File” to select a system file. Click “Start” and downloading will start.
  • Page 36: How To Download Rpm System File

    FXS901 User Manual 5.21 HOW TO DOWNLOAD RPM SYSTEM FILE This function is used to download the system file from PC to RPM. 1. Click "Edit" > "Download RPM System File". 2. Select a RPM address which must be the same as the setting on RPM and then select a RPM system file.
  • Page 37 4. When the following window is displayed, click “OK” to close it. 36/49 A6V10336897_d_en_...
  • Page 38: How To Download Led Annunciator System File

    FXS901 User Manual 5.22 HOW TO DOWNLOAD LED ANNUNCIATOR SYSTEM FILE This function is used to download the system file from PC to LED annunciator. 1. Click "Edit" > "Download LED Annunciator System File". 2. Select an address which must be the same as the setting on LED annunciator and then select a LED Annunciator system file.
  • Page 39 NOTE The downloading time depends on the number of devices the panel connects to on the UFP line. If the panel connects to only one device on the UFP line, the downloading time is about 6~7 minutes. If a panel connects to 6 devices, then the updating time is about 25~30 minutes.
  • Page 40: How To Synchronize Facp Time

    FXS901 User Manual 5.23 HOW TO SYNCHRONIZE FACP TIME This function is used to synchronize the time between PC and FACP time. 1. Click "Edit" > "Sync FACP Time". 2. Enter password and click “OK”. 3. When the sync is finished, click “OK” to close the window.
  • Page 41: How To Export Device List

    5.24 HOW TO EXPORT DEVICE LIST This function is used to view all components of the system for user. 1. Click "Edit" > "Export to txt". 2. Input file name and click “Save”. 3. When the export is finished, the following window is displayed. Click “OK” to close it. 4.
  • Page 42 FXS901 User Manual A6V10336897_d_en_ 41/49...
  • Page 43: How To Upload History File

    3. Enter a file name and click “Save”. Uploading starts. 4. When uploading is finished, the following information is displayed. Click “OK” to close it. 5. When the following window is displayed, click “OK” to view the history file or click “Cancel” to return to FXS901. 42/49 A6V10336897_d_en_...
  • Page 44: How To Upload Sensitivity Report

    FXS901 User Manual 5.26 HOW TO UPLOAD SENSITIVITY REPORT This function is used to upload the sensitivity report from FACP to PC. 1. Click "Edit" > "Upload Sensitivity Report (FACPgPC)" and then select one file format (Xls or Txt). 2. Enter password and click “OK”.
  • Page 45: How To Upload Log File

    5.27 HOW TO UPLOAD LOG FILE This function is used to upload the log file from FACP to PC. 1. Select "Upload log file (FACPgPC)" from "Edit" menu. 2. Select the desired log file and click “OK”. 44/49 A6V10336897_d_en_...
  • Page 46: How To Change Language

    FXS901 User Manual 5.28 HOW TO CHANGE LANGUAGE FXS901 software provides three languages: English, Spanish and French. 1. Click "Edit" > “Language”. Select the desired language and then the language is changed accordingly. No need to restart the software. A6V10336897_d_en_...
  • Page 47: How To Backup Panel

    5.29 HOW TO BACKUP PANEL This function is used to backup the information on the current panel. 1. Click "Edit" > “Backup Panel”. 2. Click “Save As”. Select a target folder and enter a name for the backup file in the popup window and click “Save”...
  • Page 48: How To Restore Panel

    FXS901 User Manual 5.30 HOW TO RESTORE PANEL This function is used to restore the backup settings to the current panel. 1. Click “Edit” > “Restore panel”. 2. Click “Select file”; select a backup file and click open. 3. Click “Restore”. When the following window appears, click “OK” to restart the panel or wait for 15 seconds for the panel to restart automatically.
  • Page 49: How To Config The Program Key

    5.31 HOW TO CONFIG THE PROGRAM KEY 1. Click the “Program Key” under the Hardware tree, and then select the desired function from the drop-down “Function” list in the Property window. 2. Drag allowed nodes to the “Program Key” group, and then click “Edit” > “Download configure file” to download the configure file to the panel.
  • Page 50: How To View The Version Of Fxs901

    FXS901 User Manual 5.32 HOW TO VIEW THE VERSION OF FXS901 Select "About" from "Help" menu. The version information of FXS901 is displayed. A6V10336897_d_en_ 49/49...
  • Page 51 Issued by © Beijing Siemens Cerberus Electronics Ltd., 2019 Beijing Siemens Cerberus Electronics Ltd. Technical specifications and availability subject to change without notice. No.1, Fengzhi East Road, Xibeiwang, Haidian District, 100094 BEIJING, China +86 10 64768806 www.siemens.com/buildingtechnologies Doc. No. A6V10336897_d_en_...

This manual is also suitable for:

Fx901-u2Fc901-u3Fc2005-u2Fcm901-u3Fcm901-u2Fx901-u3

Table of Contents