FDS229
Alarm sounder with
supplementary optical indication
Technical Manual
010095_j_en_--
2013-02-22
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FDS229-A

  • Page 1 FDS229 Alarm sounder with supplementary optical indication Technical Manual Building Technologies 010095_j_en_-- 2013-02-22 Control Products and Systems...
  • Page 2 Legal notice Technical specifications and availability subject to change without notice. © 2007-2013 Copyright by Siemens Switzerland Ltd Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited.
  • Page 3: Table Of Contents

    Table of contents About this document ..................5 Applicable documents ..................6 Technical terms ....................7 History of changes ....................7 Safety ......................9 Safety instructions ....................9 Safety regulations for the method of operation ..........10 Standards and directives complied with ............12 Release Notes ....................12 Structure and function .................
  • Page 4 Tones and sound intensities of the alarm sounder (32 VDC) ......41 Beam characteristics of the additional optical indicator ........43 9.2.1 FDS229-R, red (32 VDC) ..............44 9.2.2 FDS229-A, orange (32 VDC) ............45 Index ......................46 Building Technologies 010095_j_en_-- Fire Safety...
  • Page 5: About This Document

    Applicable documents 1 About this document Goal and purpose This document contains all necessary information on the alarm sounder with additional optical indicator FDS229. Following the instructions consistently will ensure that the product can be used safely and without any problems. Target groups The information in this document is intended for the following target groups: Target group...
  • Page 6: Applicable Documents

    Applicable documents Document identification The document ID is structured as follows: ID code Examples ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE -- = multilingual or international A6V10215123_a_en_-- A6V10315123_a_--_-- Conventions for text marking Markups Special markups are shown in this document as follows: Requirement for a behavior instruction Intermediate result of a behavior instruction End result of a behavior instruction Reference to a page number...
  • Page 7: Technical Terms

    Technical terms 1.2 Technical terms Term Explanation Alarm indicator FDnet/C-NET Addressable detector line Product version MC link Maintenance and commissioning link (proximity interface) 1.3 History of changes The reference document's modification index applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, have the modification index 'd' instead of 'a' if the reference document already has this modification index.
  • Page 8 History of changes The table below shows the published language versions with the corresponding modification index: Modification index en_-- de_-- fr_-- it_-- es_-- – – – – – – – – – – – – – – – – – –...
  • Page 9: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance Symbol for danger...
  • Page 10: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, assembly, installation,...
  • Page 11 Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions. Modules and spare parts Components and spare parts must comply with the technical specifications defined by Siemens.
  • Page 12: Standards And Directives Complied With

    Personal injury or damage to property caused by poor maintenance or lack of maintenance 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
  • Page 13: Structure And Function

    The alarm sounder with additional optical display is available with optical displays in various colors: FDS229-R with transparent red hood FDS229-A with transparent orange hood Features Addressable on the FDnet/C-NET Communication with the control panel via the detector loop...
  • Page 14: Details For Ordering

    Details for ordering Type Order no. Designation FDS229-R A5Q00023093 Alarm sounder with additional optical indicator, FDS229-A A5Q00023092 Alarm sounder with additional optical indicator, orange 3.1.2 Product version ES The product version ES provides the technical status of a device in terms of software and hardware.
  • Page 15: Function

    Structure and function Function 3.2 Function 3.2.1 Escalation levels and volume The alarm sounder with additional optical display can be activated for the following selectable escalation levels: Warning (Alert) Evacuation (EVAC) The tone can be configured individually for the two selectable escalation levels; the sound intensity can be configured by device.
  • Page 16: Line Separator

    Structure and function Function 3.2.2 Line separator All FDnet/C-NET devices are equipped with a line separator. The FDnet/C-NET device is equipped with electronic switches which isolate the defective part in case of a short-circuit on the detector line. The rest of the detector line remains serviceable.
  • Page 17: Diagnosis Levels

    Structure and function Function 3.2.5 Diagnosis levels The device largely monitors its function by itself. The following diagnosis levels are taken from the different control measuring processes: Normal Fault For details, see table below. When a fatal error occurs, which impairs the proper function of the alarm sounder, a fault message is signaled.
  • Page 18: Accessories

    Structure and function Accessories 3.3 Accessories 3.3.1 Addressable detector base FDB221/FDB221-AA For the installation of point detectors and alarm sounders For the recess-mounted cable entry For surface-mounted cable entry, up to 6 mm cable diameter Orange terminal block Detector base FDB221-AA additionally with a micro terminal Compatible with: –...
  • Page 19: Base Attachment Fdb291

    Structure and function Accessories 3.3.3 Base attachment FDB291 For the surface-mounted cable entry, as of 6 mm cable diameter Compatible with: – Detector base FDB2x1/FDB2x1-AA – Flat detector base FDB2x2 Order no.: A5Q00001603 See also Base attachment FDB291 [ 3.3.4 Base attachment humid FDB293 For installation in humid, wet environments and if the detector heating unit is used...
  • Page 20: Dummy Detector Fdx291

    Structure and function Accessories 3.3.6 Dummy detector FDX291 To protect the detector base from dirt External labelling for identification Does not open the contact in the detector base Compatible with: – Detector base FDB2xx – Sounder base FDSB29x Order no.: S54319-F2-A1 3.3.7 Designation plate FDBZ291 To identify the location...
  • Page 21: Detector Locking Device Fdbz293

    Structure and function Accessories 3.3.9 Detector locking device FDBZ293 For protection against theft Compatible with: – Point detectors from the 'Sinteso' product line – Alarm sounder FDS221 – Alarm sounder with additional optical indicator FDS229 – Sounder interbase FDSB221 – Sounder interbase with additional optical indicator FDSB229 Order no.: A5Q00005035...
  • Page 22: Project Engineering

    Project engineering Compatibility 4 Project engineering Please always take the country-specific provisions and the alarm organization for project planning into account. In addition, the connection factors stated in the specifications must also be taken into account. See also Technical data [ 4.1 Compatibility The device is compatible with the following control panels: FDnet: all FC20xx control panels...
  • Page 23: Installation Site

    Project engineering Installation site 4.3 Installation site The alarm sounder with additional optical indicator FDS229 can be mounted on the ceiling or wall. The device must be easily accessible for commissioning and maintenance so that it can communicate with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293 via the interface (MC link).
  • Page 24: Configuration

    Project engineering Configuration 4.5 Configuration The following chapters contain the specifications of the different tones and optical indicators. 4.5.1 Alarm sounder Tone Frequency pattern Pulse pattern Adjustable sound Norm intensity levels (typ. Sweep from values in [dBA/1m] at 12 V at 32 V Continuous 970 Hz...
  • Page 25: Optical Display

    Project engineering Configuration Tone Frequency pattern Pulse pattern Norm Adjustable sound intensity levels (typ. Sweep from values in [dBA/1m] at 12 V at 32 V Mute – – Alarm sounder is switched off so that the FDS229 can be operated simply as an optical indicator.
  • Page 26: Mounting / Installation

    Mounting / Installation Configuration 5 Mounting / Installation The alarm sounder with additional optical indicator FDS229 requires an addressed detector base. The detector base is mounted on the wall or on the ceiling. The device must be easily accessible for commissioning and maintenance so that it can communicate with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293 via the interface (MC link).
  • Page 27 Mounting / Installation Configuration Wall mounting of the alarm sounder with additional optical indicator FDS229 with a base attachment humid FDB293 and a detector base FDB221 See also Installation site [ Base attachment FDB291 [ Base attachment humid FDB293 [ Building Technologies 010095_j_en_-- Fire Safety...
  • Page 28: Base Attachment Fdb291

    Mounting / Installation Base attachment FDB291 5.1 Base attachment FDB291 Use the base attachment FDB291 for surface-mounted cable entry and cable diameters between 6 mm and 21 mm. 1. Break out the required cable entries on the base attachment FDB291. 2.
  • Page 29: Base Attachment Humid Fdb293

    Mounting / Installation Base attachment humid FDB293 5.2 Base attachment humid FDB293 For installation in wet rooms, the base attachment humid FDB293 is used. To seal the cables, especially tight metal cable glands M20 x 1.5 are used. Installation of detector base on base attachment humid FDB293 1 Base attachment humid 2 Detector base acc.
  • Page 30: Sealing Kit Fdbz295

    Mounting / Installation Sealing kit FDBZ295 5.3 Sealing kit FDBZ295 The sealing element FDBZ295 is used in conjunction with detector bases FDB2x1/FDB2x1-AA. The sealing element provides the device with protection against dirt and spray water. Installation of sealing kit FDBZ295 Installation The kit is installed by hand 1.
  • Page 31 Mounting / Installation Sealing kit FDBZ295 3. Push the connection wires through the rubber base from the rear. 4. Install the detector base. 5. Place a point detector or alarm sounder in the detector base. 6. Turn the point detector or alarm sounder to the right to screw it firmly into the detector base.
  • Page 32: Designation Plate Fdbz291

    Mounting / Installation Designation plate FDBZ291 5.4 Designation plate FDBZ291 1. Label designation plate FDBZ291 with location address of point detector or alarm sounder. 2. Note the small mark on the installed point detector or alarm sounder and slide designation plate into detector base or sounder base. Installation of designation plate FDBZ291 1 Designation plate FDBZ291 3 Marks on point detector/alarm...
  • Page 33: Designation Plate Dbz1193A

    Mounting / Installation Designation plate DBZ1193A 5.5 Designation plate DBZ1193A To provide a detector or alarm sounder on a base attachment humid FDB293 with a location address, the detector designation plate DBZ1193A is labelled and placed on the base attachment humid FDB293. FDB293 DBZ1193A Installation of designation plate DBZ1193A...
  • Page 34: Detector Locking Device Fdbz293

    Mounting / Installation Detector locking device FDBZ293 5.6 Detector locking device FDBZ293 A detector or alarm sounder can be protected against theft with the detector locking device FDBZ293. Installation of detector locking device FDBZ293 A Sounder base or detector base C Detector locking device acc.
  • Page 35: Commissioning

    Commissioning 6 Commissioning The devices are commissioned via the control panel. The exact procedure is described in the control panel documentation. Conduct a performance check once commissioning is complete. Building Technologies 010095_j_en_-- Fire Safety 2013-02-22...
  • Page 36: Maintenance / Repair

    Maintenance / Repair Status query 7 Maintenance / Repair 7.1 Status query The alarm sounder with additional optical indicator FDS229 has a proximity interface (MC link). Using this interface, it is possible to read out data from the device in a proximity method over short distances with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293.
  • Page 37: Specifications

    Specifications Technical data 8 Specifications 8.1 Technical data Detector line Operating voltage DC 12…33 V Operating current: Standby 250 A Sound activated 3,5 mA Additional optical indicator activated 3,5 mA Sound and additional optical 7.0 mA indicator activated Quiescent current connection factor Address connection factor Separator connector factor Protocol...
  • Page 38 Depending on the viewing angle, see 'Technical data annex', sub-chapter 'FDS229-R, red' FDS229-A: Orange hood 0.9 … 1.8 cd Depending on the viewing angle, see 'Technical data annex', sub-chapter 'FDS229-A, orange' Connections Detector line: Design Plug-type connection External alarm indicators:...
  • Page 39 Specifications Technical data Ambient conditions Operating temperature: -25 … +65 °C FDS229-R: Red hood -25…+55 °C FDS229-A: Orange hood Storage temperature -30…+75 °C Air humidity 95 % rel. Protection categories according to EN 60529 / IEC 60529: Detector base FDB221, FDB222,...
  • Page 40: Dimensions

    Specifications Dimensions 8.2 Dimensions Dimensions of the alarm sounder with additional optical indicator FDS229 8.3 Environmental compatibility and disposal This device is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken: Use of reusable materials Use of halogen-free plastics...
  • Page 41: Annex Technical Data

    Annex technical data Tones and sound intensities of the alarm sounder (32 VDC) 9 Annex technical data 9.1 Tones and sound intensities of the alarm sounder (32 VDC) Sound intensity measured in dBA/1 m with -0/+4 dBA (32 VDC) Tone No. 1: Continuous Horizontal Vertical Sound...
  • Page 42 Annex technical data Tones and sound intensities of the alarm sounder (32 VDC) Tone No. 5: Pulse tone Sound Horizontal Vertical intensity 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 1 (mid.) 2 (low) Tone No.
  • Page 43: Beam Characteristics Of The Additional Optical Indicator

    Annex technical data Beam characteristics of the additional optical indicator Tone No. 10: Slow-whoop Sweep-up, linear Sound Horizontal Vertical intensity 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 1 (mid.) 2 (low) Tone No. 11: Intermittent Horizontal Vertical Sound...
  • Page 44: Fds229-R, Red (32 Vdc)

    Annex technical data Beam characteristics of the additional optical indicator 9.2.1 FDS229-R, red (32 VDC) Azimuth 0° 30° 60° 90° Elevation [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [°] Beam characteristics of the additional optical indicator -1.5 -0.5 Graphic representation of the beam characteristics of the additional optical indicator...
  • Page 45: Fds229-A, Orange (32 Vdc)

    Annex technical data Beam characteristics of the additional optical indicator 9.2.2 FDS229-A, orange (32 VDC) Azimuth 0° 30° 60° 90° Elevation [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [cd/60 s] [cd/pulse] [°] Beam characteristics of the additional optical indicator -1.5...
  • Page 46: Index

    Index Index Maintenance intervals, 36 Compatibility MC link, 36 with control panels, 22 Detector exchanger and tester FDUD292, 16, 36 with sounder base FDSB29x, 23 Intelligent detector tester FDUD293, 16, 36 Control panel, 35 Proximity interface, 16 Degraded mode operation Optical display Fire control panel failure, 16 Flashing frequency, 15...
  • Page 47 Index Building Technologies 010095_j_en_-- Fire Safety 2013-02-22...
  • Page 48 Issued by © 2007-2013 Copyright Siemens Switzerland Ltd Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID...