Detailed commissioning steps
21
'One-step commissioning'
21.3 'One-step commissioning'
78 | 188
Building Technologies
Fire Safety
'OSC' mode (one-step commissioning) enables peripheral devices to be assigned
and tested in a single step. The following additional components are required:
●
Detector exchanger and tester FDUD292 with firmware version >=3.2.2
●
Bluetooth extension kit FDUD29x-E
●
'Sinteso Test' app with software version >=2.0.0
●
Mobile terminal, e.g., smartphone
You will find more information on performing 'one-step commissioning' and on
'Sinteso Test' in document A6V10424692. See chapter 'Applicable documents'.
NOTICE
Access to fire detection system data and possible misuse of data due to
unprotected Android smartphones
●
Configure your smartphone or mobile terminal according to the guidelines of
the
Siemens CERT Security Measure Plan for Android
Guidelines of the Siemens CERT Security Measure Plan for Android
Devices
●
The internal Android encryption function must be activated on your smartphone
or mobile terminal.
●
The following requirements must be met with regard to the encryption
password used:
–
At least eight characters
–
At least one upper-case letter
–
At least one lower-case letter
–
At least one special character or numeral
●
Configure the data storage space for your apps so that app data can only be
placed inside the encrypted internal memory of the device or on encrypted
memory cards.
–
Check whether the memory cards inside your device can be encrypted.
You will find the Siemens CERT Security Measure Plan for Android Devices at
https://www.cert.siemens.com/rules/mobile/.
Assignable elements
You can only assign manual and automatic channels of the type 'Sensor' with
'Sinteso Test'. Thermal/CO sensors of multi-criteria fire detectors and the
automatic channels of FDA221 and FDA241 cannot be assigned with 'Sinteso
Test'.
Executing the 'Enable one-step commissioning' command
ϖ OSC mode is to be activated for a particular element, e.g., for the 'Station'.
Start by activating the MC link with the 'Enable MC link' command and then
κ
activate OSC mode using the 'Enable one-step commissioning' command.
You will find more information on performing 'One step commissioning' in
document A6V10424692. See chapter 'Applicable documents'.
Devices.
009052_s_en_--
2016-06-02