One-Step Commissioning - Siemens FS20 Commissioning, Maintenance, Troubleshooting

Fire detection system
Hide thumbs Also See for FS20:
Table of Contents

Advertisement

Detailed commissioning steps
21

'One-step commissioning'

21.3 'One-step commissioning'
78 | 188
Building Technologies
Fire Safety
'OSC' mode (one-step commissioning) enables peripheral devices to be assigned
and tested in a single step. The following additional components are required:
Detector exchanger and tester FDUD292 with firmware version >=3.2.2
Bluetooth extension kit FDUD29x-E
'Sinteso Test' app with software version >=2.0.0
Mobile terminal, e.g., smartphone
You will find more information on performing 'one-step commissioning' and on
'Sinteso Test' in document A6V10424692. See chapter 'Applicable documents'.
NOTICE
Access to fire detection system data and possible misuse of data due to
unprotected Android smartphones
Configure your smartphone or mobile terminal according to the guidelines of
the
Siemens CERT Security Measure Plan for Android
Guidelines of the Siemens CERT Security Measure Plan for Android
Devices
The internal Android encryption function must be activated on your smartphone
or mobile terminal.
The following requirements must be met with regard to the encryption
password used:
At least eight characters
At least one upper-case letter
At least one lower-case letter
At least one special character or numeral
Configure the data storage space for your apps so that app data can only be
placed inside the encrypted internal memory of the device or on encrypted
memory cards.
Check whether the memory cards inside your device can be encrypted.
You will find the Siemens CERT Security Measure Plan for Android Devices at
https://www.cert.siemens.com/rules/mobile/.
Assignable elements
You can only assign manual and automatic channels of the type 'Sensor' with
'Sinteso Test'. Thermal/CO sensors of multi-criteria fire detectors and the
automatic channels of FDA221 and FDA241 cannot be assigned with 'Sinteso
Test'.
Executing the 'Enable one-step commissioning' command
ϖ OSC mode is to be activated for a particular element, e.g., for the 'Station'.
Start by activating the MC link with the 'Enable MC link' command and then
κ
activate OSC mode using the 'Enable one-step commissioning' command.
You will find more information on performing 'One step commissioning' in
document A6V10424692. See chapter 'Applicable documents'.
Devices.
009052_s_en_--
2016-06-02

Hide quick links: