Commissioning control panel with collective detector lines

16

Pre-configuration

16 Commissioning control panel with collective
16.1 Pre-configuration
58 | 188
Building Technologies
Fire Safety
detector lines
Prerequisites
The ↑ 'Station' is installed, but the batteries are not connected yet.
The cables for the ↑ detector lines and the mains supply have been inserted in
the 'Station', but not yet connected.
SintesoWorks is installed on the PC.
The current firmware and ↑ BDV are available on the PC.
You will find additional information about the individual steps on the specified
pages.
Commissioning
1. Create the ↑ pre-configuration. Link [➙ 58]
2. Prepare the ↑ 'Station' for commissioning – without ↑ BDV installation.
Link [➙ 77]
3. Connect the PC to the 'Station'. Link [➙ 27]
4. Load the configuration from the PC to the 'Station'. Link [➙ 30]
5. Test the function of the 'Site'. Link [➙ 91]
6. Remedy any errors you notice and load the corrected configuration from the
PC to the 'Station'. Link [➙ 30]
7. Disconnect the PC from the 'Station'. Link [➙ 27]
8. Perform the completion tasks. Link [➙ 91]
1. Create a 'Site' and the ↑ 'Station' FC2030 or FC2060 including customer text in
SintesoWorks.
2. Adapt the parameters, such as the configuration for the power supply, of the
'Station' in SintesoWorks if required.
3. Create the ↑ line card (collective) in the 'Hardware' task card.
4. Configure each individual ↑ collective detector line: Define the line type with
end element, 'Pulse memory', etc.
5. Create the ↑ 'Detection tree' as far as 'Zone' level in the 'Detection' task card.
6. Assign the 'Detection tree' to the 'Hardware tree' and the ↑ 'Control tree'.
You will find information about configuring collective detector lines in document
009078. See chapter 'Applicable documents'.
See also
1 Applicable documents [➙ 11]