Siemens FDS221-W Technical Manual

Siemens FDS221-W Technical Manual

Fds221 series. alarm sounder
Hide thumbs Also See for FDS221-W:
Table of Contents

Advertisement

FDS221
Alarm sounder
Technical Manual
008109_m_en_--
2016-02-09
Building Technologies
Control Products and Systems

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FDS221-W

  • Page 1 FDS221 Alarm sounder Technical Manual Building Technologies 008109_m_en_-- 2016-02-09 Control Products and Systems...
  • Page 2 Issued by: Siemens Switzerland Ltd. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724-2424 www.siemens.com/buildingtechnologies Edition: 2016-02-09 Document ID: 008109_m_en_-- © Siemens Switzerland Ltd, 2004 2 | 50 Building Technologies 008109_m_en_-- Fire Safety 2016-02-09...
  • Page 3: Table Of Contents

    Table of contents About this document ................5 Applicable documents ................. 7 Download center ..................7 Technical terms ..................7 History of changes ..................8 Safety ....................10 Safety instructions ..................10 Safety regulations for the method of operation ...........12 Standards and directives complied with............14 Release Notes ...................14 Structure and function .................
  • Page 4 Project engineering ................24 Compatibility ....................24 Ranges of application ................24 Installation site ................... 25 Restrictions ....................25 Configuration ..................... 25 4.5.1 Alarm sounder with ES < 30 ............26 4.5.2 Alarm sounder with ES 30 ............27 Mounting / Installation ................28 Base attachment FDB291 ................
  • Page 5: About This Document

    About this document Applicable documents 1 About this document Goal and purpose This document contains all necessary information on the FDS221 alarm sounder. Following the instructions consistently will ensure that the product can be used safely and without any problems. Target groups The information in this document is intended for the following target groups: Target group...
  • Page 6: Date Format

    About this document Applicable documents Document identification The document ID is structured as follows: ID code Examples ID_ModificationIndex_Language_COUN A6V10215123_a_de_DE A6V10215123_a_en_-- -- = multilingual or international A6V10315123_a_--_-- Date format The date format in the document corresponds to the recommendation of international standard ISO 8601 (format YYYY-MM-DD). Conventions for text marking Markups Special markups are shown in this document as follows:...
  • Page 7: Applicable Documents

    About this document Applicable documents 1.1 Applicable documents Document ID Title 007026 Data Sheet Sounder bases FDSB291, FDSB292, Alarm sounders FDS221-R, FDS221-W 007227 Technical manual Detector exchanger and tester FDUD292 008168 Installation Alarm sounder FDS221 008331 List of compatibility (for 'Sinteso™' product line)
  • Page 8: History Of Changes

    About this document History of changes 1.4 History of changes The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.
  • Page 9 About this document History of changes The table below shows the published language versions with the corresponding modification index: Modification en_-- de_-- fr_-- it_-- es_-- index X = published – = no publication with this modification index 9 | 50 008109_m_en_-- Building Technologies Fire Safety...
  • Page 10: Safety

    Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: Symbol for danger Signal word Nature and origin of the danger Consequences if the danger occurs Measures or prohibitions for danger avoidance Symbol for danger...
  • Page 11 Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger...
  • Page 12: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
  • Page 13 Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 14: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
  • Page 15: Structure And Function

    Eleven tones are programmed in the alarm sounder. Two tones can be activated for different events (e.g. alarm and evacuation). The alarm sounder is available in various colors: FDS221-R with red hood FDS221-W with white hood Features Addressed in FDnet/C-NET Communication with the control panel via the detector loop...
  • Page 16: Details For Ordering

    Order no. Designation FDS221-R A5Q00004117 Alarm sounder red FDS221-W A5Q00006711 Alarm sounder white 3.1.2 Product version ES The product version ES provides the technical status of a device in terms of software and hardware. The product version is provided as a two-digit number.
  • Page 17: Function

    Structure and function Function 3.2 Function 3.2.1 Escalation levels and sound levels The device can be activated for the following selectable escalation levels: Warning Evacuation Auxiliary sound The tone can be configured individually for the three selectable escalation levels and the sound level can be configured by device. Different tones are available, each with three sound levels.
  • Page 18: Diagnosis Levels

    Structure and function Function 3.2.4 Diagnosis levels The device monitors its operation largely autonomously. The following diagnosis levels are derived from the different control measurements: Normal Fault For details, see table below. When a fatal error occurs, which impairs the proper function of the alarm sounder, a fault message is signaled.
  • Page 19: Accessories

    Structure and function Accessories 3.3 Accessories 3.3.1 Addressable detector base FDB221/FDB221-AA For the mounting of point detectors and alarm sounders For the recess-mounted cable entry For surface-mounted cable entry, up to 6 mm cable diameter Orange terminal block Detector base FDB221-AA additionally with a micro terminal Compatible with: –...
  • Page 20: Sealing Element Fdbz295

    Structure and function Accessories 3.3.3 Sealing element FDBZ295 To protect an alarm sounder or point detector against dirt and splash water Cannot be used in conjunction with designation plate FDBZ291 A detector base FDB2x1 or FDB2x1-AA must be used in addition to the alarm sounder or point detector Compatible with: –...
  • Page 21: Protective Cage Dbz1194

    Structure and function Accessories 3.3.6 Protective cage DBZ1194 To protect the devices against mechanical damage Can only be used in conjunction with the following accessories: – Base attachment wet FDB295 – Base attachment wet BA721 Order number: BPZ:4677110001 3.3.7 Detector heating unit FDBH291 For operating point detectors in critical ambient conditions during icy conditions or when there is a danger of moisture...
  • Page 22: Designation Plate Dbz1193A

    Structure and function Accessories 3.3.9 Designation plate DBZ1193A To identify the location Compatible with: – Base attachment wet FDB295/BA721 – Base attachment, surface-mounted, humid DBZ1192 – DBW1171 base – Interbase DBS72x Order number: BPZ:4864330001 See also Designation plate DBZ1193A [ 3.3.10 Detector locking device FDBZ293 For protection against theft Compatible with:...
  • Page 23: Micro Terminal Dbz1190-Aa

    Structure and function Accessories 3.3.12 Micro terminal DBZ1190-AA Auxiliary terminal for connecting cables For T-branches of additional cabling e.g. for detector heating units, sounder base, external alarm indicators etc. For conductor cross-sections of 0.28…0.5 mm 4-pin Order number: BPZ:4677080001 3.3.13 Connection terminal DBZ1190-AB Auxiliary terminal for connecting cables For T-branches of additional cabling, e.g., for cable shielding, detector heating units,...
  • Page 24: Project Engineering

    Project engineering Compatibility 4 Project engineering Please always take the country-specific provisions and the alarm organization for project planning into account. In addition, the connection factors stated in the specifications must also be taken into account. See also Technical data [ 4.1 Compatibility The device is compatible with the following control panels: FDnet: all FC20xx control panels...
  • Page 25: Installation Site

    Project engineering Installation site 4.3 Installation site The alarm sounder FDS221 can be mounted directly on the ceiling or the wall. The device must be easily accessible for commissioning and maintenance so that it can communicate with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293 via the interface (MC link).
  • Page 26: Alarm Sounder With Es < 30

    Project engineering Configuration 4.5.1 Alarm sounder with ES < 30 Tone Frequency pattern Pulse pattern Adjustable sound levels (typ. Norm values in [dBA/1 m] Sweep from at 12 V at 32 V Continuous 970 Hz 'evacuate' BS 5839 Part 1 1988 Intermittent 950 Hz 'alert'...
  • Page 27: Alarm Sounder With Es 30

    Project engineering Configuration 4.5.2 Alarm sounder with ES 30 Tone Frequency pattern Pulse pattern Adjustable sound levels (typ. Norm values in [dBA/1 m] Sweep from at 12 V at 32 V Continuous 970 Hz 'evacuate' BS 5839 Part 1 1988 Intermittent 950 Hz 'alert'...
  • Page 28: Mounting / Installation

    Mounting / Installation Configuration 5 Mounting / Installation The alarm sounder FDS221 requires an addressed detector base. The detector base is mounted on the wall or on the ceiling. The device must be easily accessible for commissioning and maintenance so that it can communicate with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293 via the interface (MC link).
  • Page 29 Mounting / Installation Configuration Figure 6: Wall mounting of FDS221 alarm sounder with a base attachment wet FDB295 and a detector base FDB221 See also Base attachment FDB291 [ 29 | 50 008109_m_en_-- Building Technologies Fire Safety 2016-02-09...
  • Page 30: Base Attachment Fdb291

    Mounting / Installation Base attachment FDB291 5.1 Base attachment FDB291 Use the base attachment FDB291 for surface-mounted cable entry and cable diameters between 6 mm and 21 mm. 1. Break out the required cable entries on the base attachment FDB291. 2.
  • Page 31: Base Attachment Wet Fdb295

    Mounting / Installation Base attachment wet FDB295 5.2 Base attachment wet FDB295 The 'base attachment wet FDB295' is for surface-mounted feed lines in humid and cold environments. It is not possible to remove the detector using the detector tester FDUD291/detector exchanger and tester FDUD292/intelligent detector tester FDUD293.
  • Page 32 Mounting / Installation Base attachment wet FDB295 Click Click Fig. 2 FDB221 FDB222 Fig. 1 DBZ1193A FDBZ294 Fig. 3 Fig. 4 DBZ1194 Figure 8: Mounting and removal of base adapter FDB241 on detector base Fig. 1 Mounting of base attachment wet FDB295 Mounting on substructure (2 screws) Mounting of cover (4 screws) Mounting of detector base (2 screws)
  • Page 33 Mounting / Installation Base attachment wet FDB295 WARNING Danger of falling Bodily injury When installing, use a secured ladder or work platform. Only use the appropriate detector exchanger and tester or detector tester as mounting tools. Mounting (Fig. 1 and 2) 1.
  • Page 34: Sealing Element Fdbz295

    Mounting / Installation Sealing element FDBZ295 5.3 Sealing element FDBZ295 Sealing element FDBZ295 is used in conjunction with detector bases FDB2x1/FDB2x1-AA. The sealing element provides the device with protection against dirt and spray water. Figure 9: Mounting of sealing element FDBZ295 34 | 50 Building Technologies 008109_m_en_--...
  • Page 35 Mounting / Installation Sealing element FDBZ295 Mounting The kit is installed by hand 1. Fold the sealing lip back. 2. Insert the detector base into the sealing element. Make sure that the opening in the detector base lines up with the marking and opening on the rubber base. NOTICE Risk when piercing the rubber base with a tool! Consequences: Leaks in rubber base...
  • Page 36: Detector Locking Device Fdbz293

    Mounting / Installation Detector locking device FDBZ293 5.4 Detector locking device FDBZ293 A point detector or alarm sounder can be protected against theft with the detector locking device FDBZ293. Figure 10: Mounting of detector locking device FDBZ293 1 Detector base 4 Detector 2 Set screw with a hexagon socket 5 Allen key...
  • Page 37: Designation Plate Fdbz291

    Mounting / Installation Designation plate FDBZ291 5.5 Designation plate FDBZ291 1. Label designation plate FDBZ291 with location address of point detector or alarm sounder. 2. Note the small mark on the installed point detector or alarm sounder and slide designation plate into detector base or sounder base. Figure 11: Installation of designation plate FDBZ291 1 Designation plate FDBZ291 3 Marks on point detector/alarm...
  • Page 38: Designation Plate Dbz1193A

    Mounting / Installation Designation plate DBZ1193A 5.6 Designation plate DBZ1193A To provide a detector or alarm sounder on a base attachment wet FDB295 with a location address, the designation plate DBZ1193A is labeled and placed on the base attachment wet FDB295. FDB293 FDB295 DBZ1193A...
  • Page 39: Connection Of The Detector Heating Unit

    Mounting / Installation Detector heating unit FDBH291 5.7.2 Connection of the detector heating unit Connect the cables for the monitored supply from the control panel and the detector heating unit to the supplied micro terminals DBZ1190-AA. The cables can be placed in the same cable harness as the detector line or separately.
  • Page 40: Protective Cages

    Mounting / Installation Protective cages 5.8 Protective cages Protective cage DBZ1194 protects the detector against mechanical damage. EMC-protective cage FDBZ294 protects the detector against mechanical damage and electromagnetic fields. 5.8.1 Mounting of the protective cages The protective cages can only be installed on the base attachment wet FDB295. Figure 15: Mounting of the protective cages 1 Base attachment 4 Flat plug 6.3 x 0.8 mm...
  • Page 41: Commissioning

    Commissioning 6 Commissioning The devices are commissioned via the control panel. The exact procedure is described in the control panel documentation. Conduct a performance check once commissioning is complete. 41 | 50 008109_m_en_-- Building Technologies Fire Safety 2016-02-09...
  • Page 42: Maintenance / Repair

    Maintenance / Repair Status retrieval 7 Maintenance / Repair 7.1 Status retrieval The alarm sounder FDS221 has a proximity interface (MC link). Using this interface, it is possible to read out data from the device in a proximity method over short distances with the detector exchanger and tester FDUD292 or the intelligent detector tester FDUD293.
  • Page 43: Specifications

    Specifications Technical data 8 Specifications 8.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: Document 007026 Detector line Operating voltage DC 12…33 V Operating current: Standby...
  • Page 44 Specifications Technical data External alarm indicators Number of external alarm indicators that can be connected Voltage DC 10…17 V Current 9…15 mA Length of line Max. 30 m with unshielded cables (recommended), or when the shielding is connected to the positive pole of the AI on the detector base Max.
  • Page 45: Dimensions

    Specifications Dimensions Mechanical data Dimensions (Ø x H) 100 x 43 mm Housing material Polycarbonate (PC) Colors ~RAL 9010, pure white ~RAL 3000 flame red Standards European standards EN 54-3 EN 54-17 8.2 Dimensions Figure 16: Dimensions of FDS221 alarm sounder 8.3 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as...
  • Page 46: Annex Technical Data

    Annex technical data Tones and sound levels of the alarm sounder 9 Annex technical data 9.1 Tones and sound levels of the alarm sounder Legend Minimum sound level measured in dBA/1 m (DC 32 V) Minimum sound level measured in dBA/1 m (DC 12 V) Tone No.
  • Page 47 Annex technical data Tones and sound levels of the alarm sounder Tone No. 5: Pulse tone Sound level Horizontal Vertical 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 0 (max.) 1 (mid.) 2 (low) Tone No.
  • Page 48 Annex technical data Tones and sound levels of the alarm sounder Tone No. 10: Slow-whoop Sweep-up, linear Sound level Horizontal Vertical 15° 45° 75° 105° 135° 165° 15° 45° 75° 105° 135° 165° 0 (max.) 0 (max.) 1 (mid.) 2 (low) Tone No.
  • Page 49: Index

    Index Index Intelligent detector tester FDUD293 Alarm sounder MC link ............. 17, 42 With ES <30 ........... 26 Interface With ES 30........... 27 MC link ............42 Approvals ............43 Line separator CE marking ............. 43 Function ............17 Compatibility List of compatibility .........
  • Page 50 Issued by © Siemens Switzerland Ltd, 2004 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID: 008109_m_en_-- Manual FD20/FD720 Edition: 2016-02-09...