Building Technologies
Fire Safety
Initialize 'Station'
NOTICE
Connection module (card cage) FCA2006-A1 defective or installed incorrectly
Control panels identified incorrectly, e.g. FC2060 identified as FC2040.
●
Check that the connection module (card cage) FCA2006-A1 is installed
correctly.
NOTICE
Faulty initialization for networked station
During initialization, the station must not be connected to the network or any other
station.
ϖ The PC is connected locally to the ↑ 'Station'.
1. Highlight the 'Station' you want to initialize.
2. Select the 'Commissioning' > 'Initialize station' menu item.
The following window is opened:
3. Click on 'Start'.
The 'Set the station to access level 3' window opens.
4. Press <MENU> on the 'Station' and enter a valid PIN.
5. Click on 'OK' in the 'Set access level' window.
The 'Station' is initialized.
The 'Station' is restarted.
After a few minutes, the 'Buzzer' sounds twice.
6. Press <Acknowledge> on the ↑ Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.
See also
1 Loading data to the 'Station' [➙ 28]
Connectivity and communication with 'Station'
4
Initializing 'Station'
29 | 188
009052_s_en_--
2016-06-02