Symbols and their meaning ..............7 2.1.3 Classification and meaning of additional symbols ........7 Safety-relevant working instructions ............8 Overview ....................9 Setup and function................10 Manual call point FDM221 ..............10 Manual call point FDM223 ..............11 Manual call point FDM224 ..............12 Diagnosis levels ..................13 Accessories.....................14 Project planning ..................15 Installation .....................16...
Page 4
Siemens Building Technologies 007002_e_en_--.doc Fire & Security Products 11.2007...
0BAbout this document About this document Purpose of the document This document contains all information on the manual call points FDM221, FDM223 and FDM224. The consistent observance of the instructions ensures a trouble-free and safe application. Target group This documentation and the instructions contained therein are intended for the...
Page 6
Disregard of the safety regulations Before they are delivered, products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the documentation.
Safety notes This chapter describes the danger levels and the relevant safety regulations applicable for the use of the products from Siemens Building Technologies. Please read the work instructions as well as the chapter ’About this document’ before beginning any work.
1BSafety notes Safety-relevant working instructions Country-specific standards The products are developed and produced in compliance with the relevant international and European safety standards. Should additional country-specific, local safety standards or regulations concerning project planning, installation, operation and disposal of the product apply in the place of operation, then these standards or regulations must also be taken into account in addition to the safety regulations mentioned in the product documentation.
2BOverview Overview Manual call point FDM221 Manual call point FDM223 Manual call point FDM224 Housing FDMH291-x Housing FDMH293-x Housing FDMH293-x The manual call points consist of a housing and a call point unit. They have the following features: Individual call point addressing...
3BSetup and function Setup and function Manual call point FDM221 The manual call point FDM221 triggers alarm when the glass pane is pushed in (direct operation). The alarm is immediately transmitted to the control panel. Legend Housing bottom Switching unit...
3BSetup and function Manual call point FDM223 The manual call point FDM223 triggers alarm when the glass pane is pushed in and the alarm button is pressed (indirect operation). The alarm is immediately transmitted to the control panel. Legend Housing bottom Switching unit Terminals Stopping lever...
3BSetup and function Manual call point FDM224 The manual call point FDM224 triggers alarm when the glass pane is pushed in (direct operation). The alarm is immediately transmitted to the control panel. To reset the manual call point FDM224 after an alarm, a new glass pane must be inserted.
3BSetup and function Diagnosis levels The detector largely auto-monitors its function. The following diagnosis levels are derived from the different control measurings: Normal Exchange required Fault Details see table below. When a fatal error occurs, which makes the proper function of the detector impossible, a fault message is signalled.
4BProject planning Project planning Compatibility Compatible with all control panel types that support the FDnet detector line. Refer to 'List of compatibility' (doc. no. 008331) for details. Range of application The manual call points are intended for use in places where a fire can be detected by people who can manually trigger an alarm.
Preparation Depending on the cabling (recessed or surface cabling), the housing must be prepared for inserting the cables. FDM221 1. Break out the key from the housing cover. 2. Press the two key knobs into the recesses (see figure below).
Installation 6.2.1 Fixation FDM221 1. Install the housing at a height of 1.3 … 1.6 m on an even surface. 2. Pull the cables through the entry opening(s) into the housing. 3. For surface mounting, use screwed cable glands (max. M20 with nut).
When a protective cover is used, proceed as follows: 1. Open the housing. 2. Place the protective cover (1) in the lid (2) (see figure below). 3. Close the housing (3) with the lid (2). FDM221 FDM223/FDM224 007002_e_en_--.doc Fire Safety & Security Products...
As long as a manual call point is out of service, it must be provided with a Caution note "OUT OF SERVICE“! Only one wire may be connected to each terminal point; only this way is it possible to guarantee a faultless connection over the complete life cycle. Connection diagrams FDM221 FDM223/FDM224 FDnet FDnet FDnet FDnet FDM221 1.
Page 20
5BInstallation FDM223/FDM224 1. Connect the feeding line to the terminals in the call point unit (1), in accordance with the connection diagram. 2. When inserting the call point unit (1) into the housing (2), pay attention to the feeding line. 3.
Localization red, flashing Performance check FDM221 1. Set the detector line to Test. 2. Insert the key from below into the housing. The glass pane falls down, actuating the switch. The LED flashes. 3. Pull off the key. The glass is pushed back into its initial position and the detector is again ready for operation.
Page 22
6BCommissioning FDM224 1. Set the detector line to Test. 2. Pull the cover of the keyhole to the right. 3. Open the door with the key. The alarm signal is transmitted. 4. Close the door of the detector. The detector is ready for operation again. 5.
After alarm activation the manual call point must be set in operational availability again. This procedure is different for each of the two detector types. FDM221 To set the detector back to operational availability, proceed as follows: 1. Open the housing.
Page 24
7BMaintenance / Troubleshooting FDM223 To set the detector back to operational availability, proceed as follows: 1. Open the housing. 2. Remove the glass pane. 3. Insert a new glass pane. 4. Push the black locking lever (2) in the upper right corner to the right until you hear it clicking.
7BMaintenance / Troubleshooting Replacing the glass pane FDM221 The glass pane is provided with a number. It is covered by a foil layer. This foil holds the glass splinters together when the glass pane is pushed in, enabling trouble-free removal of the glass.
Page 26
7BMaintenance / Troubleshooting FDM223/FDM224 The glass pane is square-shaped and can be inserted in any direction. Proceed as follows: 1. Pull the cover of the keyhole to the right. 2. Open the housing with the key enclosed in the delivery. Keep the key in a safe place.
Spare parts Designation FDM221 FDM223/FDM224 Application Cover with key FDMK291 — To open the housing and for the performance check of FDM221. — DMZ1195 Glass pane FDMG291 DMZ1196-AC A part of the actuation mechanism, protects the switch from soiling. 007002_e_en_--.doc Fire Safety &...
8BSpecifications Specifications Technical data Operating voltage 12 … 33 VDC Detector line 200 μA Operating current (quiescent) Maximum current connection factor Quiescent current connection factor Address connection factor Separator connector factor Protocol FDnet System compatibility see doc. no. 008331 'List of compatibility'. Line voltage: Line separator nominal...
Page 29
8BSpecifications Operating temperature -25 … +70 °C Ambient conditions Storage temperature -30 … +75 °C Air humidity ≤95 % rel. Protection category EN60529/IEC529: FDM221, housing FDMH291-x IP44 – FDM223/FDM224, IP44 – housing FDMH293-x without sealing DMZ1197-AD FDM223/FDM224 IP65 – housing FDMH293-x...
8BSpecifications Dimensional drawings 9.2.1 Dimensions FDM221, housing FDMH291-x FDM223/FDM224, housing FDMH293-x 9.2.2 Master gauge for recesses FDM221, housing FDMH291-x FDM223/FDM224, housing FDMH293-x Environmental compatibility Electronic components and synthetic materials can be separated. The synthetic material parts are identified and can be disposed of accordingly.
Page 31
8BSpecifications 007002_e_en_--.doc Fire Safety & Security Products 11.2007...
Need help?
Do you have a question about the FDM221 and is the answer not in the manual?
Questions and answers