Detailed commissioning steps
21
Preparing 'Station' for commissioning
21 Detailed commissioning steps
21.1 Preparing 'Station' for commissioning
76 | 188
Building Technologies
Fire Safety
In the following chapters, you will find detailed commissioning steps that are
referred to in several chapters.
1. Connect the cables for the ↑ detector lines and the peripheral devices.
2. Connect the power supply (mains and batteries).
The ↑ 'Station' starts and reads in the internal hardware.
During start-up, the 'FAULT' LED flashes and the display shows the
progress.
During start-up, the firmware version F-FXS2001 is displayed.
3. Wait until the display indicates the selection of the ↑ BDV.
4. Press the 'Install' softkey and confirm with the 'Yes' softkey.
The 'Station' restarts.
During this process, the 'FAULT' LED flashes and the display shows the
progress.
5. Wait until only the green 'System On' LED lights up, the display shows the
normal condition, and the 'Station' can be operated.
6. Press <MENU> and select the 'Login/logout' menu item.
You are prompted to enter a PIN.
7. Enter the PIN and confirm with <ok>.
The 'User successfully logged in' message is displayed.
The main menu is shown on the display.
8. Check the firmware of the 'Station' to ensure that it is up to date. To do this,
select the 'Topology' > 'Hardware tree' > 'Station' > 'More Options' > 'Show
details' menu items.
The 'Station' version and configuration data are displayed.
9. Update the firmware if necessary.
10. Enter the date and time. To do this, select the 'Settings/administration' >
'System commands' > 'Set system time' menu items.
Additional messages may be displayed depending on the configuration of the
↑ 'Station'.