Commissioning control panel with collective detector lines
16

Troubleshooting procedure

16.3.1 'Line Fault' error message

16.4 Troubleshooting procedure

16.4.1 Checking the collective detector line

60 | 188
Building Technologies
Fire Safety
If the error message 'Line fault' is displayed for collective detector lines once the
↑ 'Station' has started, the cause may be a change in line resistance.
Greater resistance, e.g. due to corrosion of the base connections or faulty end-
of-line element
Less resistance e.g. due to a defective 'Detector' or a faulty end-of-line element
See also
1 Reference measurement with EOL 4k7 and 3k3 [➙ 59]
1 Checking line resistance [➙ 61]
You will find additional information about the individual steps on the specified
pages.
1. Test the ↑ collective detector line. Link [➙ 60]
2. Test the line resistance. Link [➙ 61]
3. Test the line continuity. Link [➙ 61]
4. Measure the insulation values. Link [➙ 62]
5. Commission the collective detector line step-by-step. Link [➙ 63]
When testing collective detector lines on the ↑ line card (collective) FCL2002, you
must observe the following points:
Detectors must not be triggered too soon after each other.
The total time required to check a collective detector is 50 s.
Once a detector has been triggered, the internal ↑ alarm indicator flashes for
15 s and the line is automatically reset.
The length of time after which the line is ready for the next detector to be
triggered varies depending on the line type.
Type
Transzorb
EOL22Ex
EOL 4k7
EOl 3k3
Table 3: Total time required to check a collective detector
Total time required
45 s
40 s
50 s
50 s
009052_s_en_--
2016-06-02