Installation

3 Installation

3.1 BACnet Interface

3
3

3.1.1 Safety Instructions

See chapter 2 Safety for general safety instructions.
WARNING
INDUCED VOLTAGE
Induced voltage from output motor cables that run
together can charge equipment capacitors even with the
equipment turned off and locked out. Failure to run
output motor cables separately or use screened cables
could result in death or serious injury.
run output motor cables separately, or
use screened cables
CAUTION
SHOCK HAZARD
The frequency converter can cause a DC current in the
PE conductor. Failure to follow the recommendation
below means that the RCD may not provide the
intended protection.
When a residual current-operated protective
device (RCD) is used for protection against
electrical shock, only an RCD of Type B is
permitted on the supply side.
Overcurrent protection
Additional protective equipment such as short
circuit protection or motor thermal protection
between frequency converter and motor is
required for applications with multiple motors.
Input fusing is required to provide short circuit
and overcurrent protection. If not factory-
supplied, the installer provides fuses. See
maximum fuse ratings in VLT
and FCM 106 Operating Instructions.
Wire Type and Ratings
All wiring must comply with local and national
regulations regarding cross section and ambient
temperature requirements.
Power connection wire recommendation:
minimum 75 °C rated copper wire.
8
®
VLT
DriveMotor FCP 106 & FCM 106 BACnet Operating Instructions
See VLT
Instructions for recommended wire sizes and types.

3.1.2 Special Conditions

Electrical ratings
The frequency converter rating, shown on the nameplate,
is based on a typical 3-phase mains power supply within
the specified voltage, current and temperature range,
expected for most applications.
The frequency converters also support other special
applications, which affect the electrical ratings of the
frequency converter.
Special conditions which can affect the electrical ratings:
Other applications can also affect the electrical ratings.
Consult the relevant sections in this manual and in the
VLT
information about the electrical ratings.
Installation requirements
The overall electrical safety of the frequency converter
requires special installation considerations regarding:
®
DriveMotor FCP 106
Consult the relevant clauses in this manual and in the VLT
DriveMotor FCP 106 and FCM 106 Operating Instructions for
information about the installation requirements.
MG03O102 - Danfoss A/S © 12/2013. All rights reserved.
®
DriveMotor FCP 106 and FCM 106 Operating
Single phase applications
High temperature applications which require
derating of the electrical ratings
Marine applications with more severe environ-
mental conditions.
®
DriveMotor FCP 106 and FCM 106 Design Guide for
Fuses and circuit breakers for overcurrent and
short circuit protection
Selection of power cables (mains, motor,
brakeloadsharing, and relay)
Grid configuration (grounded delta transformer
leg, IT, TN, and so on)
Safety of low-voltage ports (PELV conditions).
®