Parameters
8-53 Start Select
Option:
[2]
Logic AND Activates Start command via the serial communi-
3
3
[3]
Logic OR
*
8-54 Reversing Select
Option:
[0]
Digital
*
input
[1]
Bus
[2]
Logic AND Activates Reverse command via the serial
[3]
Logic OR
8-55 Set-up Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic AND Activates the set-up selection via the serial
[3]
Logic OR
*
48
VLT HVAC Basic Drive Programming Guide
Function:
cation port, AND additionally via one of the
digital inputs.
Activates Start command via the serial communi-
cation port OR via one of the digital inputs.
Function:
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the serial communication port.
NOTE
This parameter is active only when
8-01 Control Site is set to [0] Digital and
control word.
Activates Reverse command via a digital input.
Activates Reverse command via the serial
communication port.
communication port, AND additionally via one of
the digital inputs.
Activates Reverse command via the serial
communication port OR via one of the digital
inputs.
Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
NOTE
This parameter is active only
when8-01 Control Site is set to [0] Digital
and control word.
Activates the set-up selection via a digital input.
Activates the set-up selection via the serial
communication port.
communication port, AND additionally via one of
the digital inputs.
Activate the set-up selection via the serial
communication port OR via one of the digital
inputs.
MG.18.B1.02 - VLT
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset
Reference selection via the terminals (digital
input) and/or via the serial communication port.
[0]
Digital
Activates Preset Reference selection via a digital
input
input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port.
[2]
Logic AND
Activates Preset Reference selection via the
serial communication port, AND additionally via
one of the digital inputs.
[3]
Logic OR
Activates the Preset Reference selection via the
*
serial communication port OR via one of the
digital inputs.

3.8.4 8-7* BACnet

8-70 BACnet Device Instance
Range:
1
[0 - 0x3FFFFEUL. ] Enter a unique ID number for the BACnet
*
8-72 MS/TP Max Masters
Range:
127.0
[0.0 - 127.0 ] Define the address of the master which
*
8-73 MS/TP Max Info Frames
Range:
1.0
[1.0 - 65534.0 ] Define how many info/data frames the
*
8-74 "I am" Service
Option:
[0]
Send at power-
*
up
[1]
Continuously
8-75 Intialisation Password
Range:
Function:
admin
[1 - 1 ] Enter the password needed for execution of
*
Drive Re-initialisation.
®
is a registered Danfoss trademark
Function:
device.
Function:
holds the highest address in this network.
Decreasing this value optimises polling for
the token.
Function:
device is allowed to send while holding
the token.
Function:
Choose whether the device should send
the "I-Am" service message only at power-
up or continuously with an interval of
approx. 1 min.