Busbar protection REB670
Customized
Product version: 1.2
IEC06000192 V1 EN
Figure 13.
Example of status of primary switchgear objects
1 User settable switchgear names
2 Switchgear object status

16. Station communication

Overview
Each IED is provided with a communication interface,
enabling it to connect to one or many substation level
systems or equipment, either on the Substation Automation
(SA) bus or Substation Monitoring (SM) bus.
Following communication protocols are available:
• IEC 61850-8-1 communication protocol
• LON communication protocol
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol
Theoretically, several protocols can be combined in the same
IED.
IEC 61850-8-1 communication protocol
The IED is equipped with single or double optical Ethernet
rear ports (order dependent) for IEC 61850-8-1 station bus
communication. The IEC 61850-8-1 communication is also
possible from the optical Ethernet front port. IEC 61850-8-1
protocol allows intelligent electrical devices (IEDs) from
different vendors to exchange information and simplifies
system engineering. Peer-to-peer communication according
24
to GOOSE is part of the standard. Disturbance files uploading
is provided.
Serial communication, LON
Existing stations with ABB station bus LON can be extended
with use of the optical LON interface. This allows full SA
functionality including peer-to-peer messaging and
cooperation between existing ABB IED's and the new IED
670.
SPA communication protocol
A single glass or plastic port is provided for the ABB SPA
protocol. This allows extensions of simple substation
automation systems but the main use is for Substation
Monitoring Systems SMS.
IEC 60870-5-103 communication protocol
A single glass or plastic port is provided for the
IEC60870-5-103 standard. This allows design of simple
substation automation systems including equipment from
different vendors. Disturbance files uploading is provided.
DNP3.0 communication protocol
An electrical RS485 and an optical Ethernet port is available
for the DNP3.0 communication. DNP3.0 Level 2
communication with unsolicited events, time synchronizing
and disturbance reporting is provided for communication to
RTUs, Gateways or HMI systems.
Multiple command and transmit
When 670 IED's are used in Substation Automation systems
with LON, SPA or IEC60870-5-103 communication protocols
the Event and Multiple Command function blocks are used as
the communication interface for vertical communication to
station HMI and gateway and as interface for horizontal peer-
to-peer communication (over LON only).
IEC 62439-3 Parallel Redundant Protocol
Redundant station bus communication according to IEC
62439-3 Edition 1 and IEC 62439-3 Edition 2 are available as
options in 670 series IEDs. IEC 62439-3 parallel redundant
protocol is an optional quantity and the selection is made at
ordering. Redundant station bus communication according to
IEC 62439-3 uses both port AB and port CD on the OEM
module.
Select IEC 62439-3 Edition 1 protocol at
the time of ordering when an existing
redundant station bus DuoDriver installation
is extended.
Select IEC 62439-3 Edition 2 protocol at
the time of ordering for new installations
with redundant station bus.
IEC 62439-3 Edition 1 is NOT compatible
with IEC 62439-3 Edition 2.
1MRK505273-BEN D