General Technical Data - Danfoss VLT Brook Crompton Motor FCM 300 Design Manual

Table of Contents

Advertisement

Installation

2.1.2 General Technical Data

2
2
Mains supply, TT, TN and IT* (L1, L2, L3)
Supply voltage 380-480 V units
Supply frequency
Max. imbalance of supply voltage
Power factor / cos
No. of switching operations on supply input L1, L2, L3
*) Not valid for RFI class 1B units
Torque characteristics
Starting torque/overload torque
Continuous torque
Control card, digital/pulse inputs
Number of programmable digital inputs
Terminal nos.
Voltage level
Voltage level, logic 0
Voltage level, logic 1
Maximum voltage on input
Input resistance, R
Scanning time
Control card, pulse input
No. of programmable pulse inputs
Terminal nos.
Max. frequency on terminal 3, open collector/push pull 24 V
Resolution
Accuracy (0.1-1 kHz), terminal 3
Accuracy (1-12 kHz), terminal 3
Control card, analogue inputs
No. of programmable analogue voltage inputs
Terminal nos.
Voltage level
Input resistance, R
No. of programmable analogue current inputs
Terminal no.
Current range
Input resistance, R
Resolution
Accuracy on input
Scanning time
Control card, digital/pulse and analogue outputs
No. of programmable digital and analogue outputs
Terminal nos.
Voltage level at digital output/load
Current at analogue output
Maximum load to frame (terminal 8) at analogue output
Accuracy of analogue output
Resolution on analogue output.
Relay output
No. of programmable relay outputs
Terminal number (resistive and inductive load)
Max. terminal load (AC1) on 1-3, 1-2
12
VLT
i
i
i
MG03BA02 - VLT
®
DriveMotor FCM Series
®
is a registered Danfoss trademark
3x380/400/415/440/460/480 V ±10%
50/60 Hz
±2% of rated supply voltage
max. 0.9/1.0 at rated load
approx. 1 time/2 min
160% for 1 min
see above
X101-2, -3, -4, -5
0-24 V DC (PNP positive logics)
<5 V DC
>10 V DC
28 V DC
approx. 2 kΩ
20 mses
8 kHz/70 kHz
Max. error: 0.5% of full scale
Max. error: 0.1% of full scale
0-10 V DC (scalable)
approx. 10 kΩ
0 - 20 mA (scalable)
approx. 300 Ω
Max. error 1% of full scale
0 - 24 V DC/25 mA
0 - 20 mA
R
LOAD
Max. error: 1.5% of full scale
1-3 (break), 1-2 (make)
250 V AC, 2A, 500 VA
4
1
X101-3
10 bit
1
X101-2
1
X101-1
9 bit
20 ms.
1
X101-9
500 Ω
8 bit
1

Advertisement

Table of Contents
loading

Table of Contents