Programming
for a period longer than the time set in parameter 317, the
function selected in parameter 318 will be activated.
Description of choice:
Set the desired time.
Settings:
No function
Ready signal
Enable, no warning
Running
Running, no warning
Running on reference, no warning
Fault
Fault or warning
Current limit
Thermal warning
Reversing
Control word bit 11
Control word bit 12
Mechanical brake
Sleep mode
Table 3.9 323 Terminal X102, Relay Function (RELAY FUNC.)
The relay output can be used to give the present status or
a warning.
Relay
1 - 3 break, 1 - 2 make
Max. 250 V AC, 5 Amp.
Table 3.10
Description of choice:
Unit Ready signal, the FC motor is ready for use.
Enable/no warning, the FC motor is ready for use; no start
or stop command has been given (start/ disable). No
warning.
Running, A start command has been given.
Running no warning, A start command has been given. No
warning.
Running on reference, no warning, speed according to
reference.
Fault, output is activated by alarm.
Fault or warning, the output is activated by alarm or
warning.
®
VLT
DriveMotor FCM Series
318
Value:
Function:
This parameter allows a choice of the function to be
activated if the value of the reference signal connected to
the input, terminal 1, falls below 50% of the setting in
parameter 336 for a period longer than the time set in
parameter 317.
If a time-out function (parameter 318) occurs at the same
time as a bus time-out function (parameter 514), the time-
out function (parameter 318) will be activated.
Current limit, the current limit in parameter 221 has been
exceeded.
Thermal warning, above the temperature limit in the
frequency converter.
Reverse. Logic '1' = relay activated, 24 V DC on the output
when the direction of rotation of the motor is clockwise.
Logic '0' = relay not activated, no signal on the output,
when the direction of rotation of the motor is counter-
clockwise.
Control word bit 11, if bit 11 = "1" in the control word
(both Fieldbus Profile and FC Profile) the relay will be
activated.
Control word bit 12, if bit 12 = "1" in the control word
(both Fieldbus Profile and FC Profile) the relay will be
activated.
Mechanical brake, enables control of an optional external
mechanical brake (see also parameter 138 and 139).
Sleep mode, active when the unit is in sleep mode. See
3.5.2 Sleep Mode.
327
Value:
®
MG03BA02 - VLT
is a registered Danfoss trademark
Function after time out
Off (OFF)
Stop and trip (STOP AND TRIP)
(NO OPERATION)
(UNIT READY)
(ENABLE/NO WARNING)
(RUNNING)
(RUNNING NO WARNING)
(RUNNING ON REFERENCE)
(FAULT)
(FAULT OR WARNING)
(CURRENT LIMIT)
(THERMAL WARNING)
(REVERSE)
(CONTROL WORD BIT 11)
(CONTROL WORD BIT 12)
(MECHANICAL BRAKE)
(SLEEP MODE)
Pulse reference/feedback, max. frequency
100-70000 Hz
[0]
[5]
3
3
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[20]
[21]
[100-70000]
47