Programming
as the serial communication port can be used for switching
between Setups.
005
Programming Setup
Value:
Factory Setup (FACTORY SETUP)
Setup 1 (SETUP 1)
Setup 2 (SETUP 2)
Active Setup (ACTIVE SETUP)
Function:
The choice is of the Set-up in which programming (change
of data) is to occur during operation. It is possible to
programme the two Set-ups independently of the Set-up
selected as the Active Set-up (selected in parameter 004).
Description of choice:
The [0] Factory Setup contains the factory data and can be
used as a data source if the other Set-ups are to be
returned to a known state.
[1] Setups 1 and [2] 2 are individual Setups which can be
used as required. They can be programmed freely,
regardless of the Set-up selected as the Active Set-up and
thus controlling the functions of the FC motor.
006
Copying of Setups
Value:
No copying (NO COPY)
Copy to Setup 1 from # (COPY TO SETUP 1)
Copy to Setup 2 from # (COPY TO SETUP 2)
Copy to Setup all from # (COPY TO ALL)
# = the Setup selected in parameter 005
Function:
A copy is made from the Set-up selected in parameter 005
to one of the other Set-ups or to all the other Set-ups
simultaneously.
007
LCP copy
Value:
No copying (NO COPY)
Upload all parameters (UPLOAD ALL PARAM)
Download all parameters (DOWNLOAD ALL)
Download power-independent par.
(DOWNLOAD SIZE INDEP.)
Function:
Parameter 007 is used if it is desired to use the integrated
copying function of the control panel. You can therefore
easily copy parameter value(s) from one FC motor to
another.
Description of choice:
Select [1] Upload all parameters if all parameter values are
to be transmitted to the control panel. Select [2] Download
all parameters if all transmitted parameter values are to be
copied to the FC motor on which the control panel has
been mounted. Select [3] Download power-independent par.
®
VLT
DriveMotor FCM Series
if only the power-independent parameters are to be
downloaded. This is used if downloading to a FC motor
that has a different rated power than the one from where
the parameter Set-up originates.
[0]
008
[1]
Value:
[2]
[5]
Function:
This parameter chooses the factor to be multiplied by the
motor frequency, f
parameters 009-012 have been set for Frequency x Scaling
[5].
Description of choice:
Set the desired scaling factor.
009
Value:
[0]
[1]
[2]
[5]
[0]
[1]
[2]
[3]
Function:
This parameter allows a choice of the data value to be
displayed in line 2 of the display.
Parameters 010-012 enable the use of three additional data
values to be displayed in line 1.
For display read-outs, press the [DISPLAY/STATUS] button,
see 3.1.7 Control Key Functions.
®
MG03BA02 - VLT
is a registered Danfoss trademark
Display scaling of motor frequency
0.0-100.00
1.00
, for presentation in the display, when
M
Display line 2
None
Reference [%] (REFERENCE [%])
Reference [unit] (REFERENCE [UNIT])
Feedback [unit] (FEEDBACK [UNIT])
Frequency [Hz] (FREQUENCY [Hz])
Frequency x Scaling [-] (FREQUENCY X SCALE)
Motor current [A] (MOTOR CURRENT [A])
Torque [%] (TORQUE [%])
Power [kW] (POWER [kW])
Power [HP] (POWER [hp] [US])
Motor voltage [V] (MOTOR VOLTAGE [V])
DC link voltage [V] (DC LINK VOLTAGE [V])
Thermal load, FC [%] (FC THERMAL [%])
Hours run [Hours] (RUNNING HOURS)
Digital input [Binary code] (DIGITAL INPUT [BIN])
External reference [%] (EXTERNAL REF [%])
Status word [Hex] (STATUS WORD [HEX])
Heat sink temp. [°C] (HEATSINK TEMP [°C])
Alarm word [Hex] (ALARM WORD [HEX])
Control word [Hex] (CONTROL WORD [HEX])
Warning word 1 [Hex]
(WARNING WORD 1 [HEX])
Warning word 2 [Hex]
(EXTENDED STATUS WORD [HEX])
Analog input 1 [mA] (ANALOG INPUT 1 [mA])
Analog input 2 [V] (ANALOG INPUT 2 [V])
3
3
[1-10000]
[100]
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[11]
[12]
[14]
[15]
[16]
[21]
[22]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
37