Programming
1200 Baud (1200 BAUD)
2400 Baud (2400 BAUD)
4800 Baud (4800 BAUD)
9600 Baud (9600 BAUD)
3
3
Function:
This parameter is for programming the speed at which
data is to be transmitted via the serial connection. Baud
rate is defined as the number of bits transferred per
second.
Description of choice:
The transmission speed of the FC motor is to be set at a
value that corresponds to the transmission speed of the
PLC/PC.
502
Coasting
503
Quick-stop
504
DC-brake
505
Start
506
Reversing
507
Selection of Setup
508
Selection of speed
Value:
Digital input (DIGITAL INPUT)
Bus (SERIAL PORT)
Logic and (LOGIC AND)
Logic or (LOGIC OR)
Function:
Parameters 502-508 allow a choice between controlling the
FC motor via the terminals (digital input) and/or via the
bus.
If Logic and or Bus is selected, the command in question
can only be activated if transmitted via the serial
communication port. In the case of Logic and, the
command must additionally be activated via one of the
digital inputs.
Description of choice:
[0] Digital input is selected if the control command in
question is only to be activated via a digital input.
[1] Bus is selected if the control command in question is
only to be activated via a bit in the control word (serial
communication).
[2] Logic and is selected if the control command in
question is only to be activated when a signal is
transmitted (active signal = 1) via both a control word and
a digital input.
Digital input
505-508
0
0
1
1
Table 3.30
70
®
VLT
DriveMotor FCM Series
Bus
Control command
0
0
1
0
0
0
1
1
®
MG03BA02 - VLT
[3] Logic or is selected if the control command in question
[2]
is to be activated when a signal is given (active signal = 1)
[3]
either via a control word or via a digital input.
[4]
[5]
Digital input
505-508
0
0
1
1
Table 3.31
Parameter 502 = Logic and
Digital input
0
0
1
1
Table 3.32
Parameter 502 = Logic or
Digital input
[0]
0
0
[1]
1
[2]
1
[3]
Table 3.33
509
Bus jog 1
Value:
0.0-parameter 202
10.0 HZ
Function:
This is where to set a fixed speed (jog) that is activated via
the serial communication port.
This function is the same as in parameter 213.
Description of choice:
The jog frequency f
JOG
between f
(parameter 201) and f
MIN
510
Bus jog 2
Value:
0.0-parameter 202
10.0 HZ
Function:
This is where to set a fixed speed (jog) that is activated via
the serial communication port.
This function is the same as in parameter 213.
is a registered Danfoss trademark
Bus
Control command
0
0
1
1
0
1
1
1
Bus
Control command
0
1 Coasting
1
0 Motor running
0
0 Motor running
1
0 Motor running
Bus
Control command
0
1 Coasting
1
1 Coasting
0
1 Coasting
1
0 Motor running
can be selected in the range
(parameter 202).
MAX
[0 -]
[100]
[0 -]
[100]