Programming
Function:
This is where the desired function is to be selected if Local
control has been chosen in parameter 002. See also the
description of parameter 100.
Description of choice:
If Local not active [0] is selected, a possible setting of Local
reference via parameter 003 is blocked. It is only possible to
change to Local not active [0] from one of the other setting
options in parameter 013, when the FC motor has been set
to Remote control [0] in parameter 002.
LCP control and open loop [1] is used when the speed is to
be adjustable (in Hz) via parameter 003, when the FC
motor has been set to Local control [1] in parameter 002.
If parameter 100 has not been set to Speed regulation open
loop [0], switch to Speed regulation open loop [0].
LCP digital control and open loop [2] functions as LCP
control and open loop [1], the only difference being that
when parameter 002 has been set to Local operation [1],
the motor is controlled via the digital inputs.
LCP control/as parameter 100 [3] is selected if the reference
is to be set via parameter 003.
LCP digital control/as parameter 100 [4] functions as LCP
control/as parameter 100 [3], although, when parameter
002 has been set to Local operation [1], the motor may be
controlled via the digital inputs.
The present motor frequency and direction of rotation
must be maintained. If the present direction of rotation
does not correspond to the reversing signal (negative
reference), the motor frequency f
Shift from LCP digital control and open loop to Remote
control:
The selected configuration (parameter 100) will be active.
Shifts are effected without any abrupt movement.
Shift from Remote control to LCP control/as parameter 100
or LCP digital control/as parameter 100.
The present reference will be maintained. If the reference
signal is negative, the local reference will be set at 0.
Shift from LCP control/as parameter 100 or LCP remote
control as parameter 100 to Remote control.
The reference will be replaced by the active reference
signal from the remote control..
014
Local stop
Value:
Not possible (DISABLE)
Possible (ENABLE)
Function:
This parameter disables/enables the local stop function in
question from the control panel. This key is used when
parameter 002 has been set for [0] Remote control or [1]
Local .
Description of choice:
If [0] Disable is selected in this parameter, the [STOP] key
will be inactive.
®
VLT
DriveMotor FCM Series
will be set at 0 Hz.
M
[0]
[1]
®
MG03BA02 - VLT
is a registered Danfoss trademark
015
Local jog
Value:
Not possible (DISABLE)
Possible (ENABLE)
Function:
In this parameter, the jog function can be enabled/
disabled on the control panel.
Description of choice:
If [0] Disable is selected in this parameter, the [JOG] key
will be inactive.
016
Local reversing
Value:
Not possible (DISABLE)
Possible (ENABLE)
Function:
In this parameter, the reversing function can be enabled/
disabled on the control panel. This key can only be used if
parameter 002 has been set to [1] Local operation and
parameter 013 to [1] LCP control with open loop or [3] LCP
control as parameter 100.
Description of choice:
If [0] Disable is selected in this parameter, the [FWD/ REV]
key will be inactive.
See parameter 200.
017
Local reset of trip
Value:
Not possible (DISABLE)
Possible (ENABLE)
Function:
In this parameter, the reset function can be selected/
removed from the keyboard. This key can be used when
parameter 002 has been set for [0] Remote control or [1]
Local control .
Description of choice:
If [0] Disable is selected in this parameter, the [RESET] key
will be inactive.
018
Lock for data change
Value:
Not locked (NOT LOCKED)
Locked (LOCKED)
Function:
In this parameter, the software can "lock" the control,
which means that data changes cannot be made via LCP 2
(however, this is still possible via the serial communication
port).
[0]
3
3
[1]
[0]
[1]
[0]
[1]
[0]
[1]
39