Danfoss VLT Brook Crompton Motor FCM 300 Design Manual page 40

Table of Contents

Advertisement

Programming
Description of choice:
Reference [%] corresponds to the total reference (sum of
digital/analogue/preset/bus/freeze ref./ catch-up and slow-
down).
Reference [unit] gives the sum of the references using the
3
3
unit stated on the basis of configuration in parameter 100
(Hz, Hz and rpm).
Feedback [unit] gives the status value of terminal 1 and 2
using the unit/scale selected in parameter 414, 415 and
416.
Frequency [Hz] gives the motor frequency, i.e. the output
frequency to the motor.
Frequency x Scaling [-] corresponds to the present motor
frequency f
multiplied by a factor (scaling) set in
M
parameter 008.
Motor current [A] states the phase current of the motor
measured as effective value.
Torque [%] gives the current motor load in relation to the
rated motor torque.
Power [kW] states the actual power consumed by the
motor in kW.
Power [HP] states the actual power consumed by the
motor in HP.
Motor voltage [V] states the voltage supplied to the motor.
DC link voltage [V] states the intermediate circuit voltage in
the FC motor.
Thermal load, FC [%] states the calculated/ estimated
thermal load on the FC motor. 100% is the cut-out limit.
Hours run [Hours] states the number of hours that the
motor has run since the latest reset in parameter 619.
Digital input [Binary code] states the signal states from the
4 digital terminals (2, 3, 4 and 5). Input 5 corresponds to
the bit at the far left. '0' = no signal, '1' = connected signal.
External reference [%] gives the sum of the external
reference as a percentage (the sum of analogue/ pulse/
bus).
Status word [Hex] gives the status word sent via the serial
communication port in Hex code from the FC motor.
Heat sink temp. [°C] states the present heat sink
temperature of the FC motor. The cut-out limit is 90 ± 5°C;
cutting back in occurs at 60 ± 5°C.
Alarm word [Hex] indicates one or several alarms in a Hex
code. See 4.2.4 Warning Word, Extended Status Word and
Alarm Word.
Control word [Hex] indicates the control word for the FC
motor. See 3.6 Serial communication - FCM 300 Design
Guide.
Warning word 1 [Hex] indicates one or more warnings in a
Hex code. See 4.2.4 Warning Word, Extended Status Word
and Alarm Word for further information.
Extended status word [Hex] indicates one or more status
states in a Hex code. See 4.2.4 Warning Word, Extended
Status Word and Alarm Word for further information.
Analog input 1 [mA] states the signal value on terminal 1.
38
®
VLT
DriveMotor FCM Series
Analog input 2[V] states the signal value on terminal 2.
010
Value:
Reference [%]
See parameter 009.
Function:
This parameter enables a choice of the first of three data
values to be shown on the display, line 1, position 1.
Description of choice:
There is a choice of 24 different data values, see parameter
009.
011
Value:
Motor current [A]
See parameter 009
Function:
This parameter enables a choice of the second of the three
data values to be shown on the display, line 1, position 2.
For Display read-outs, press the [DISPLAY/STATUS] button,
see 3.1.7 Control Key Functions.
Description of choice:
There is a choice of 24 different data values, see parameter
009.
012
Value:
Power [kW]
See parameter 009
Function:
This parameter enables a choice of the third of the three
data values to be shown on the display, line 1, position 3.
Display read-outs are made by pressing the [DISPLAY/
STATUS] button, see 3.1.7 Control Key Functions.
Description of choice:
There is a choice of 24 different data values, see parameter
009.
013
Value:
Local not active (DISABLE)
LCP control and open loop.
(LCP CTRL/OPEN LOOP)
LCP digital control and open loop.
(LCP+DIG CTRL/OP.LOOP)
LCP control/as parameter 100.
(LCP CTRL/AS P100)
LCP digital control/as parameter 100.
(LCP+DIG CTRL/AS P100)
®
MG03BA02 - VLT
is a registered Danfoss trademark
Display line 1.1
Display line 1.2
Display line 1.3
Local Control/Configuration as parameter
100
[1]
[1]
[8]
[0]
[1]
[2]
[3]
[4]

Advertisement