Programming
If closed loop has been selected the maximum reference
cannot be set higher than the maximum feedback
(parameter 415).
Description of choice:
Set the desired value.
3
3
207
Ramp-up time 1
Value:
0.15-3600.00 s
3.00 s
Function:
The ramp-up time is the acceleration time from 0 Hz to
the rated motor frequency f
presupposes that the current limit is not reached (to be set
in parameter 221).
Illustration 3.17
Description of choice:
Program the desired ramp-up time.
208
Ramp-down time 1
Value:
0.15-3600.00 s
3.00 s
Function:
The ramp-down time is the deceleration time from the
rated motor frequency f
provided there is no over-voltage in the inverter because
of regenerative operation of the motor, and the current
limit is not reached (to be set in parameter 221).
Description of choice:
Program the desired ramp-down time.
209
Ramp-up time 2
Value:
0.15-3600.00 s
3.00 s
Function:
The ramp-up time is the acceleration time from 0 Hz to
the rated motor frequency f
44
®
VLT
DriveMotor FCM Series
[5 -360000]
(parameter 104). This
M,N
[5 - 360000]
(parameter 104) to 0 Hz
M,N
[5 -360000]
(parameter 104). This
M,N
MG03BA02 - VLT
presupposes that the current limit is not reached (to be set
in parameter 221).
Description of choice:
Program the desired ramp-up time.
Shift from ramp 1 to ramp 2 by activating ramp 2 via a
digital input.
210
Ramp-down time 2
Value:
0.15-3600.00 s
[300]
3.00 s
Function:
The ramp-down time is the deceleration time from the
rated motor frequency f
provided there is no over-voltage in the inverter because
of regenerative operation of the motor, and the current
limit is not reached (to be set in parameter 221).
Description of choice:
Program the desired ramp-down time.
Shift from ramp 1 to ramp 2 by activating ramp 2 via a
digital input
211
Jog ramp time
Value:
0.15-3600.00 s
3.00 s
Function:
The jog ramp time is the acceleration/deceleration time
from 0 Hz to the rated motor frequency f
104), provided there is no over-voltage in the inverter
because of regenerative operation of the motor, and the
current limit is not reached (to be set in parameter 221).
[300]
Illustration 3.18
The jog ramp time starts if a jog signal is given via the
digital inputs or the serial communication port.
[300]
®
is a registered Danfoss trademark
[5-360000]
(parameter 104) to 0 Hz
M,N
[5-360000]
(parameter
M,N
[300]
[300]