General Specifications and ...
9.2 General Specifications
Line power supply (L1, L2, L3)
Supply voltage
AC line voltage low / line drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage
drops below the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated
supply voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency
drive's lowest rated supply voltage.
Supply frequency
Max. imbalance temporary between line phases
True Power Factor ()
Displacement Power Factor (cos) near unity
Switching on input supply L1, L2, L3 (power-ups) ≤ enclosure type A
Switching on input supply L1, L2, L3 (power-ups) ≥ enclosure type B, C
Switching on input supply L1, L2, L3 (power-ups) ≥ enclosure type D, E, F
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 480/600 V
maximum.
Motor output (U, V, W)
Output voltage
9
9
Output frequency
Switching on output
Ramp times
*
Dependent on power size.
Torque characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
* Percentage relates to the adjustable frequency drive's nominal torque.
Cable lengths and cross-sections
Max. motor cable length, shielded/armored
Max. motor cable length, non-shielded/unarmored
Max. cross-section to motor, line power, load sharing and brake *
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
* See Line Power Supply tables for more information!
176
Design Guide
Danfoss A/S © Rev. 06/2014 All rights reserved.
200–240 V ±10%, 380–480 V ±10%, 525–690 V ±10%
3.0% of rated supply voltage
overvoltage category III / pollution degree 2
maximum 135% up to 0.5 s
®
VLT
®
VLT
2
2
0.0023 in
[1.5 mm
]/16 AWG (2 x 0.0012 in
0.00016 in
0.0008 in
50/60 Hz ±5%
≥ 0.9 nominal at rated load
(> 0.98)
maximum twice/min.
maximum once/min.
maximum once/2 min.
0–100% of supply voltage
0–590 Hz
*
Unlimited
1–3600 s
Maximum 110% for 1 min.
*
*
*
Maximum 110% for 1 min.
HVAC Drive: 492 ft [150 m]
HVAC Drive: 984 ft [300 m]
2
2
[0.75 mm
])
2
[1 mm
2
]/18 AWG
2
[0.5 mm
2
]/20 AWG
2
2
0.00039 in
[0.25 mm
]
MG11BC22
Need help?
Do you have a question about the VLT FC 102 Series and is the answer not in the manual?