Electrical Installation
Enclosure
Power (hp [kW])
type
A2
1.5–5 [1.1–4.0]
A3
7.5–10 [5.5–7.5]
B3
15–25 [11–18]
B4
30–50 [22–37]
C3
60–75 [45–55]
C4
100–125 [75–90]
A4
1.5–5 [1.1–4]
A5
1.5–10 [1.1–7.5]
B1
15–25 [11–18.5]
B2
30–40 [22–30]
C1
50–75 [37–55]
C2
100–125 [75–90]
Table 6.20 380–480 V, Enclosure Types A, B and C
MG11BC22
Design Guide
Recommended
Recommended
fuse size
gG-10 (1.5–4 [1.1–3])
gG-16 (5 [4])
gG-16
gG-40
gG-50 (30 [22])
gG-63 (40 [30])
gG-80 (50 [37])
gG-100 (60 [45])
gG-150 (60 [45])
gG-160 (75 [55])
gG-160 (75 [55])
aR-200 (100 [75])
aR-250 (125 [90])
gG-10 (1.5–4 [1.1–3])
gG-16 (5 [4])
gG-10 (1.5–4 [1.1–3])
gG-16 (5–10 [4–7.5])
gG-40
gG-50 (30 [22])
gG-63 (40 [30])
gG-80 (50 [37])
gG-100 (60 [45])
gG-160 (75 [55])
aR-200 (100 [75])
aR-250 (125 [90])
Danfoss A/S © Rev. 06/2014 All rights reserved.
Recommended circuit
Max. fuse
breaker Moeller
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-63
PKZM4-50
gG-125
NZMB1-A100
NZMB2-A200
aR-250
NZMB2-A250
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-160
NZMB2-A200
aR-250
NZMB2-A250
Max trip level [A]
25
25
50
100
150
250
6
82 [25]
25
63
100
160
250
107
6
Need help?
Do you have a question about the VLT FC 102 Series and is the answer not in the manual?