Danfoss VLT FC 102 Series Design Manual page 182

Hvac drive, 1.1–90 kw
Hide thumbs Also See for VLT FC 102 Series:
Table of Contents

Advertisement

General Specifications and ...
Surroundings
Enclosure type A
Enclosure type B1/B2
Enclosure type B3/B4
Enclosure type C1/C2
Enclosure type C3/C4
Enclosure kit available.
Vibration test enclosure A, B, C
Relative humidity
Aggressive environment (IEC 60068-2-43) H
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating
- with full output power of typical IE2 motors (up to 90% output current)
- at full continuous FC output current
1) For more information on derating see chapter 9.6 Special Conditions
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
9
9
Maximum altitude above sea level with derating
Derating for high altitude, see chapter 9.6 Special Conditions
EMC standards, Emission
EMC standards, Immunity
See chapter 9.6 Special Conditions
Control card performance
Scan interval
Control card, USB serial communication
USB standard
USB plug
CAUTION
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
The USB connection is not galvanically isolated from protection ground. Use only isolated laptop/PC as connection to
the USB connector on or an isolated USB cable/drive.
180
Design Guide
5%–95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
S test
2
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
Danfoss A/S © Rev. 06/2014 All rights reserved.
IP 20/Chassis, IP 21kit/Type 1, IP55/Type12, IP 66/Type12
IP 21/Type 1, IP55/Type12, IP 66/12
IP 21/Type 1, IP55/Type 12, IP66/12
IP21/NEMA 1/IP 4
-13–+149/158 °F [-25–+65/70 °C]
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
IP20/Chassis
IP20/Chassis
on top of enclosure
X
1.0 g
class Kd
max. 131 °F [55 °C]
1)
max. 122 °F [50 °C]
1)
max. 113 °F [45 °C]
1)
32 °F [0 °C]
14 °F [-10 °C]
3300 ft [1000 m]
10,000 ft [3000 m]
5 ms
1.1 (Full speed)
USB type B "device" plug
MG11BC22

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 102 Series and is the answer not in the manual?

Table of Contents