Danfoss VLT FC 102 Series Design Manual page 95

Hvac drive, 1.1–90 kw
Hide thumbs Also See for VLT FC 102 Series:
Table of Contents

Advertisement

Electrical Installation
Enclosure
200–240 V
380–480 V
type
(hp [kW])
(hp [kW])
A2
1.5–3
1.5–5
[1.1–2.2]
[1.1–4]
A3
4–5
7.5–10
[3–3.7]
[5.5–7.5]
A4
1.5–3
1.5–5
[1.1–2.2]
[1.1–4]
A5
1.5–5
1.5–10
[1.1–3.7]
[1.1–7.5]
B1
7.5–15
15–25
[5.5–11]
[11–18]
B2
20
30–40
[15]
[22–30]
B3
7.5–15
15–25
[5.5–11]
[11–18]
B4
11–25
30–50
[15–18]
[22–37]
C1
25–40
50–75
[18–30]
[37–55]
C2
50–60
100–125
[37–45]
[75–90]
C3
30–40
60–75
[22–30]
[45–55]
C4
50–60
100–125
[37–45]
[75–90]
Table 6.1 Tightening-up Torque
MG11BC22
Design Guide
525–690 V
Cable for
(hp [kW])
-
-
-
-
Line power, brake resistor, load sharing, motor cables
Relay
Ground
15–40
Line power, brake resistor, load sharing cables
[11–30]
Motor cables
Relay
Ground
-
Line power, brake resistor, load sharing, motor cables
Relay
Ground
-
Line power, brake resistor, load sharing, motor cables
Relay
Ground
-
Line power, brake resistor, load sharing cables
Motor cables
Relay
Ground
50–125
Line power, motor cables
[37–90]
Load sharing, brake cables
Relay
Ground
-
Line power, brake resistor, load sharing, motor cables
Relay
Ground
-
Line power, motor cables
Load sharing, brake cables
Relay
Ground
Danfoss A/S © Rev. 06/2014 All rights reserved.
Tightening up torque
(lb/ft [Nm])
1.33 [1.8]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
3.32 [4.5]
3.32 [4.5]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
1.33 [1.8]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
3.32 [4.5]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
7.38 [10]
7.38 [10]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
10.33 [14] (up to
4/0 AWG [95 mm
2
])
17.7 [24] (over 4/0 AWG
2
[95 mm
])
10.33 [14]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
7.38 [10]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
10.33 [14] (up to
4/0 AWG [95 mm
2
])
17.7 [24] (over 4/0 AWG
2
[95 mm
])
10.33 [14]
0.37–0.44 [0.5–0.6]
1.48–2.21 [2–3]
93
6
6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents