System
> Statistics
> Self consumpti.
> Self sufficien.
> Ener. from grid
> Ener. to grid
> Ener. to load
> PV en. to load
> PV ener.
> Settings
Password 0000
> Set time
> Set cash
> Set RS485 com
> Country Select
> New password
> Info
> SD Update Info
> Energy Policy
> Measures
3. Set RS485 Com
This section of the menu allows you to adjust the settings relating to the
RS485 communication serial portsSet port 1" and "Set port 2").
• RS485 address: Allows you to set the address for serial communica-
Inverter
tion of the individual inverters connected to the RS485 line. Use the UP
and DOWN buttons to scroll the numerical scale. (The addresses that
can be assigned are 2 to 63).
> Statistics
• Protocol: It allows you to set the type of protocol to be used for the
> Lifetime
RS485 line. The proprietary "Aurora (slave)" protocol or "ModBus RTU"
protocol can be selected.
> Partial
• Parity: It allows you to set the Parity bit (None, Even, Odd).
> Today
• Baud Rate: Allows you to set the Baud Rate (2400/4800/9600/19200/
34800/57600/115200).
> Last 7 days
> Last 30 days
4. Country Select.
> Last 365 days
Allows you to modify the grid standard (this option can be selected when
the inverter is first switched on) within 24 hours while the inverter is ope-
> User Period
rating.
• Set Std: allows you to set the required grid standard.
> Settings
• Residual Time: indicates the time remaining until the "Country Select"
Password 0000
feature is blocked.
> Vstart
• Reset Country: Unlocks the grid standard selection (resets the
24 hours available for changing the grid standard). To carry out the reset,
> Input mode
it is necessary to enter the 2nd level password.
> Input UV Delay
> Service
5. New Password
This section of the menu allows you to change the password for acces-
> Remote ON/OFF
sing the settings menu (default 0000).
We ADVISE you to be very careful in memorizing the new password. If
> MPPT Scan
*
the Password is lost you will not have access to the inverter, since there
> Power Limit.
is no Reset function for security reasons.
> Reactive Power
System > Info
> Autotest
The Info menu is only available if previous firmware updates have been
> Alarms
carried out via SD Card.
> Backup
> Info
Select Info to access the following sub-menus:
> Part No.
1. SD Update Info
> Serial No.
This section of the menu (visible only when SD card is inserted) is used
to display the outcome of the firmware update of the various devices in
> Firmware
the inverter carried out using the SD Card,
The word "OK" signals programming was successful (if the opposite is
true, it shows "FAIL").
2. Energy Policy
This section of the menu allows you to check the settings relating to the
energy management policy. In particular:
• PV Peak Power: power of the PV generator
• Grid Power Lim.: limit of output power.
- 125 -
Скачано с сайта интернет магазина https://axiomplus.com.ua/
Display
> Settings
Password 0000
> Backlight
> Contrast
> Buzzer
> Power Graph
> Language
**
7 - Operation
****
Meter
> Settings
Password 0000
> Meter model
> Meter Address
> Meter com
> Info
> Type
> Part No.
> Serial No.
> FW Rel.
> Measures
> Voltage
> Active Power
> Line current
> Load current
> Frequency