For long distance connections, it is preferable to use a shielded twisted pair cable with
characteristic impedance of Z0=120 Ohm like the one shown in the following table:
Shield continuity must be provided along the communication line and must be grounded at a
single point using terminal 19 or 20 ( ).
Скачано с сайта интернет магазина https://axiomplus.com.ua/
Connect the signals respecting the following positions:
Terminal
Terminal
Description
name
number
14
-T/R RS485 METER communication line
RS485
16
+T/R RS485 METER communication line
METER
Reference (RTN) of the RS485 METER
18
communication line
SH
+T/R
-T/R
RTN
SH
+T/R
-T/R
RTN
- 98 -
5 - Installation
Signal
Symbol
Positive data
+T/R
Negative data
-T/R
Reference
RTN
Shield
SH ( )