ABB REACT-3.6-TL Product Manual page 156

From 3.6 to 4.6 kw, solar inverters
Hide thumbs Also See for REACT-3.6-TL:
Table of Contents

Advertisement

- Error code
- Error message
Name of Alarm and Cause
- Warning
Output overcurrent:
- E006
The alarm occurs when the inverter's output current
- Output OC
exceeds the inverter's threshold for maximum output
-
Yellow LED
current.
- E007
Saturation recorded on the IGBT components:
- IGBT Sat
The alarm appears when one of the active devices of
-
Yellow LED
the inverter is in saturation state.
- E009
Error inside the inverter:
- Internal error
Error inside the inverter
-
Yellow LED
Low "Bulk" voltage (DC-DC circuit):
The alarm can be caused by causes external to
- E010
the inverter: a reduced input voltage on the inverter
- Bulk Low
(just above the activation voltage) but which is not
accompanied by a sufficient availability of power from
-
Yellow LED
the photovoltaic generator (typical condition of the
stages with limited irradiation)
- E011
Long wait for "Booster" regime to start:
- Ramp Fail
Error internal to inverter relating to start up time for
-
Yellow LED
DC-DC circuit regime (Booster)
Error in the "Booster" circuit (DC-DC side)
- E012
recorded by the "Inverter" circuit (DC-AC side):
- DcDc Fail
Error inside the inverter regarding the operation of the
-
Yellow LED
DC-DC circuit part (Booster).
Incorrect configuration of inputs (set in parallel
rather than independent):
- E013
The alarm is generated solely when the inverter
is configured with parallel inputs. In this particular
- Wrong Mode
configuration the inverter checks the input voltage of
-
Yellow LED
each of the two channels and if the two voltages differ
by more than 20Vdc, the alarm is raised .
Excessive temperature inside the inverter:
External temperature over 60°C. This parameter also
- E014
depends on the power which the inverter must supply
- Over Temp.
since the measurement of temperatures is done
-
Yellow LED
internally and is influenced by the heat dissipated by
the components of the inverter itself
- E015
Fault recorded on the "Bulk" capacitor:
- Bulk Cap Fail
Error inside the inverter regarding a problem in the
-
Yellow LED
bulk capacitors.
Error in the "Inverter" circuit (DC-AC side)
- E016
recorded by the "Booster" circuit (DC-DC side):
- Inverter Fail
The alarm is generated when a problem is detected in
-
Yellow LED
the inverter circuit part (DC/AC).
Long wait for "Inverter" regime to start up:
Error internal to inverter relating to start-up time for the
DC-AC circuit regime (Inverter)
- E017
The alarm can be caused by causes external to
- Start Timeout
the inverter: a reduced input voltage on the inverter
-
Yellow LED
(just above the activation voltage) but which is not
accompanied by a sufficient availability of power from
the photovoltaic generator (typical condition of the
stages with limited irradiation)
- 156 -
Скачано с сайта интернет магазина https://axiomplus.com.ua/
Solution
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
Once the error appears, the inverter attempts to resume
normal operation.
- Should the error occur sporadically, it may be caused by a
brusque transition of the grid voltage or of the input voltage,
but is not due to a malfunction by the inverter.
- If the error is connected to an internal fault, it will continue to
appear and so it is necessary to contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the error signal occurs sporadically, it may be due to
causes external to the inverter (limited irradiation and so
limited power availability from the PV generator).
- If the problem occurs systematically even in conditions of
high irradiation and with input voltage which is significantly
higher than the activation voltage, contact customer
assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
• Check that the setting of the "IN MODE" switch is specifically
set to "PAR" and that the jumpers between the two input
channels have been included.
- If the configuration of the inverter is correct, check that the
input strings have the usual number of standard panels of the
usual brand and with the same inclination/orientation.
- If both the configuration of the inverter and the characteristics
of the PV generator conform with the specifications, contact
customer assistance.
• Check that the inverter is not exposed to direct sunlight. Wait
for the temperatures to which the inverter is exposed to return
to the operating range and for the inverter to cool down.
- If the problem persists (once the ambient temperature has
returned to within the range), contact customer assistance.
You must remember to wait for the time necessary to allow the
inverter to cool down.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
- If the error signal occurs sporadically, it may be due to
causes external to the inverter (limited irradiation and so
limited power availability from the PV generator).
- If the problem occurs systematically even in conditions of
high irradiation and with input voltage which is significantly
higher than the activation voltage, contact customer
assistance.