ABB REACT-3.6-TL Product Manual page 143

From 3.6 to 4.6 kw, solar inverters
Hide thumbs Also See for REACT-3.6-TL:
Table of Contents

Advertisement

****
****
Meter
Battery
> Settings
> General
Password 0000
> Settings
> Meter model
Password 0000
> Meter Address
> Battery Model
> Meter com
> Battery Packs
> Info
> Info
> Type
> Nom. Cap
> Part No.
> Measures
> Serial No.
> Ibat
> FW Rel.
> Vbat
> Measures
> Pbat
> Voltage
> RE
> Active Power
> SOC
> Line current
> SOH
> Load current
> RT
> Frequency
> Pack 1
> Statistics
> Energy dischar.
> E-day
> E-7d
> E-30d
> E-365
> E-tot
> Settings
Password 0000
> Pack 1 enable
> Smoke Sensor
> Info
> Device Name
> Serial No.
> FW Rel.
> Nom. Capacity
> Init. Capacity
> Status
> Warning
> Alarms
> Measures
> Ibat
> Vbat
> Pbat
> Tbat
> FCC
> RC
> RE
> TED
> SOC
> SOH
> TUT
> TDT
> RT
> CC
5. SOC
State of charge - Value of state of charge of the battery (expressed as a
****
percentage)
Load Manager
WIFI Logger
6. SOH
State of health - Percentage value that indicates the state of health of the
> info
> Settings
battery pack. The value is given by the ratio between FCC (actual battery
> Relay Status
> Restore AP
> Info
capacity) and IC (nominal battery capacity)
> Part No.
> Serial No.
7. RT
> View IP
Remaining time - Time remaining before the battery runs out calculated
> View Mode
based on actual absorption.
Battery > Pack 1 > Statistics
1. Energy dischar.
This section of the menu displays the statistics relating to the battery
running out (Pack 1). In particular:
• E-day: Energy used today from battery
• E-7d: Energy used from battery in last 7 days.
• E-30d: Energy used from battery in last 30 days.
• E-365d: Energy used from battery in last 365 days.
• E-tot: Total energy used from battery
Battery > Pack 1 > Settings
Selecting Settings brings up the first screen relating to the password.
The default password is "0000".
Enter the password using the keys on the display:
• DOWN scrolls down the numerical scale (from 9 to 0)
• UP scrolls up the numerical scale (from 0 to 9)
• ENTER confirms and moves to next digit
• ESC returns to the previous digit (from right to left)
• Press ESC several times to return to the previous menus
1. Pack 1 Enable
Enables or disables the operation of the REACT-BATT 1:
2. Smoke Sensor
Enables or disables the control of the brightness sensor installed inside
the REACT-BATT (relating to battery pack 1)
Battery > Pack 1 > Info
Select Info to access the following sub-menus:
1. Device Name
Displays the name of battery pack 1 (4-digit code)
- 143 -