IFM Electronic Ecomat 300 AL1030 Device Manual page 64

Io-link master ethercat
Table of Contents

Advertisement

IO-Link Master EtherCat
The following emergency messages are supported by the device
Error code
Error register
(hex)
10011008
Bit D1 is set
10111018
Bit D1 is set
10211028
Bit D2 is set
10311038
Bit D1 is set
10411048
Bit D1 is set
10511058
Bit D1 is set
10611068
Bit D1 is set
23012308
Bit D1 is set
30013008
Bit D2 is set
3010
Bit D2 is set
3020
Bit D2 is set
3030
Bit D2 is set
30313038
Bit D2 is set
3040
Bit D2 is set
30413048
Bit D2 is set
3050
Bit D2 is set
30613068
Bit D3 is set
40014008
Bit D3 is set
50015008
Bit D2 is set
81018108
Bit D7 is set
64
Diagnostic data
Localisation
(hex)
00, 09, 0x, 00, 00,
Channel level
x = 1  8
00, 0A, 0x, 00, 00,
Channel level
x = 1  8
00, 0B, 0x, 00, 00,
Channel level
x = 1  8
00, 0E, 0x, 00, 00,
Channel level
x = 1  8
00, 0F, 0x, 00, 00,
Channel level
x = 1  8
00, 11, 0x, 00, 00,
Channel level
x = 1  8
00, 12, 0x, 00, 00,
Channel level
x = 1  8
00, 07, 0x, 00, 00,
Channel level
x = 1  8
00, 01, 0x, 00, 00,
Channel level
x = 1  8
00, 02, 00, 00, 00
Device level
00, 03, 00, 00, 00
Device level
00, 04, 00, 00, 00
Device level
00, 09, 0x, 00, 00,
Channel level
x = 1  8
00, 05, 00, 00
Device level
00, 10, 0x, 00, 00,
Channel level
x = 1  8
00, 0D, 00, 00, 00
Device level
00, 0C, 0x, 00, 00,
Channel level
x = 1  8
00, 06, 0x, 00, 00,
Channel level
x = 1  8
00, 10, 0x, 00, 00,
Channel level
x = 1  8
00, 08, 0x, 00, 00,
Channel level
x = 1  8
Description
General error
Parameter missing
Parameter setting error
Upper limit exceeded
Lower limit not reached
Simulation active
Ground fault
Short circuit at pin 4
Sensor supply overload
Sensor supply overvoltage
Sensor supply undervol-
tage
Actuator supply overvoltage
Sensor supply overvoltage
Actuator supply undervol-
tage
Sensor supply undervol-
tage
Short circuit of the actuator
supply
Supply voltage failure
Excess temperature
Fuse blown
Short circuit

Advertisement