EventCodes (hex)
Definition
42214FFF
Reserved
5000
Device hardware fault – Device exchange
5001500F
Reserved
5010
Component malfunction – Repair or exchange
5011
Non volatile memory loss – Check batteries
5012
Batteries low – Exchange batteries
501350FF
Reserved
5100
General power supply fault – Check availa-
bility
5101
Fuse blown/open – Exchange fuse
5102510F
Reserved
5110
Primary supply voltage over-run – Check
tolerance
5111
Primary supply voltage under-run – Check
tolerance
5112
Secondary supply voltage fault (Port Class B)
– Check tolerance
5113...5FFF
Reserved
6000
Device software fault – Check firmware
revision
6001631F
Reserved
6320
Parameter error – Check data sheet and
values
6321
Parameter missing – Check data sheet
6322634F
Reserved
6350
Parameter changed – Check configuration
635176FF
Reserved
7700
Wire break of a subordinate device – Check
installation
7701770F
Wire break of subordinate device 115
– Check installation
7710
Short circuit – Check installation
7711
Ground fault – Check installation
77128BFF
Reserved
8C00
Technology specific application fault – Reset
Device
8C01
Simulation active – Check operational mode
8C028C0F
Reserved
IO-Link Master EtherCat
Device
TYPE
Status
Value
4
Error
4
Error
4
Error
2
Warning
4
Error
4
Error
2
Warning
2
Warning
2
Warning
4
Error
4
Error
4
Error
4
Error
4
Error
4
Error
4
Error
4
Error
4
Error
3
Warning
UK