28.2 Confirm diagnostic messages
In overwrite mode (SI5, Bit 4 = 0)
When the subindex of the most recent acknowledged message is written into
the field [Newest Acknowledged Message] (0x10F3:SI3), all older diagnostic
messages are acknowledged as well Here, it is not verified if they have already
been read (indication takes place via 0x10F3:SI5:Bit 5 = 0)
If a subindex is written that does not contain a diagnostic message, the SDO-
Abort-Code 06090030
SI
History
6
Message_12
7
Message_13
8
Message_14
9
Message_15
10
Message_16
11
Message_17
12
Message_18
13
Newest_19
14
Message_09
15
Message_10
16
Message_11
In the acknowledgement mode (SI5, Bit 4 = 1)
When the subindex of the most recent acknowledged message is written into
the field [Newest Acknowledged Message] (0x10F3:SI3), all older diagnostic
messages are acknowledged as well
Here, it is not verified if they have already been read (indication takes place via
0x10F3:SI5:Bit 5 = 0)
If a subindex is written that does not contain a diagnostic message, the SDO-
Abort-Code 06090030
28.3 Delete diagnostic messages
In overwrite mode (SI5, Bit 4 = 0)
If a zero is written into the field [Newest Acknowledged Message] (0x10F3:SI3), all
messages are deleted without verification
In the acknowledgement mode (SI5, Bit 4 = 1)
is returned
hex
Status
read
read
read
read
read
read
read
read
is returned
hex
IO-Link Master EtherCat
Status
acknowledge
acknowledge
acknowledge
acknowledge
acknowledge
acknowledge
write SI1 = 12
acknowledge
acknowledge
acknowledge
acknowledge
UK