IFM Electronic Ecomat 300 AL1030 Device Manual page 43

Io-link master ethercat
Table of Contents

Advertisement

Index
Sub index
Object
(hex)
(hex)
name
8000
IO-Link Configuration Data Port 1
00
Number of
entries
04
Device ID
05
Vendor ID
0A
Module Ident
24
Process
Data in
length
25
Process
Data out
length
28
Master
Control
Data
Rights
Description/value
type
UINT8
RO
Number of sub-indexes of the object
UINT32
R/W
Device ID of the IO-Link device
Verification will only be carried out if the value
is != 0
UINT32
R/W
Vendor ID of the IO-Link device
Verification will only be carried out if the value
is != 0
UINT32
R/W
Module identification number
Get known numbers from the ESI data The
device does not evaluate this entry
UINT8
R/W
Number and structure of the input process
data of the device
Bit
04
5
6
7
UINT8
R/W
Number and structure of the output process
data of the device
Bit
0  4
5
6
7
UINT16
R/W
Operating mode of the IO-Link port
00
01
02
IO-Link Master EtherCat
Description
Process data length
Reserved
SIO indicator
(Device supports the
standard IO mode)
Byte indicator (length is inter-
preted as byte +1)
Description
Process data length
Reserved
SIO indicator
(device supports the standard
IO mode)
Byte indicator (length is inter-
preted as byte +1)
Deactivated
Digital_In
(function as digital input)
Digital_Out
(function as digital output)
UK