IFM Electronic Ecomat 300 AL1030 Device Manual page 45

Io-link master ethercat
Table of Contents

Advertisement

Index
Sub index
Object
(hex)
(hex)
name
9000
IO-Link Configuration Data Port 1
00
Number of
entries
01
Fixed Station
Address
05
Vendor ID
06
Product
code
07
Revision
number
08
Serial
number
0A
Module Ident
20
IO-Link
revision
22
Cycle time
(ms)
24
Process
Data in
length
25
Process
Data out
length
28
Master
Control
9010
IO-Link Information Data Port 2
Data
Rights
Description/value
type
UINT8
RO
Number of sub-indexes of the object
UINT16
RO
First IO-Link port
UINT32
RO
Vendor ID structure signalled by the device
corresponds with 0x8000:05
UINT32
RO
Product code signalled by the device
UINT32
RO
Revision number signalled by the device
UINT32
RO
Serial number signalled by the device
UINT32
R/W
Structure corresponds with 0x8000:10
UINT8
RO
IO-Link revision signalled by the device
Bit
0  3
4  7
UINT8
RO
Cycle time signalled by the device
in milliseconds
Bit
0  5
6  7
UINT8
RO
Input process data length
signalled by the device
corresponds with 0x8000:36
UINT8
R/W
Output process data length structure
signalled by the device corresponds with
0x8000:37
UINT16
R/W
Operating mode of the IO-Link port
Hex
00
01
02
03
04
IO-Link Master EtherCat
Description
Minor revision
Major revision
Description
Multiplier
Time Base
Description
Deactivated
Digital_In (function as
digital input)
Digital_Out (function as
digital output)
IO-Link
DI with IO-Link (non cy-
clic IOL communication,
also called SIO mode)
45
UK

Advertisement

Table of Contents
loading

Table of Contents