IFM Electronic Ecomat 300 AL1030 Device Manual page 39

Io-link master ethercat
Table of Contents

Advertisement

Index
Sub-in-
Object
(hex)
dex (hex)
name
2800
IO-Link parameter port 1
00
Number of
entries
01
Data storage
Data
Rights
Description/value
type
UINT8
RO
Number of sub-indexes of the object
UINT8
R/W
The data storage mechanism allows the
exchange of parameters between the master
and device
To use this function, connected devices must
at least support the IO-Link specification v11
Hex Description
00
01
02
03
04
IO-Link Master EtherCat
Deactivated (default)
Download only
The parameter data is sent from the
IO-Link master to the device
In the event of an inconsistency
between the parameter data of the IO-
Link device and the IO-Link master, the
data from the IO-Link master is taken
as the default
That means that it is possible to
exchange the IO-Link device In this
mode, no upload is possible
Upload only
The parameter data is sent from the
IO-Link device to the IO-Link master
In the event of an inconsistency
between the parameter data of the IO-
Link device and the IO-Link master, the
data from device is used as the default
That means that it is possible to
exchange the IO-Link master
In this mode, no download is possible
Download and upload
The parameter data is saved both in
the IO-Link master and the device
In the event of an inconsistency
between the parameter data of the
IO-Link device or the IO-Link master,
the data from the master is used as the
default
Deactivated and deleted
The data storage mechanism is
deactivated and the master deletes all
stored parameters for the respective
port