Output current for each channel [mA]
Output current for each device [A]
Nominal load, ohmic [W]
inductive nominal load [VA]
Signal delay [µs]
Signal delay [µs]
Switching frequency
Switching frequency
Limitation of the voltage induced on circuit interruption [V]
Output voltage when switched off [V]
Output current when switched off [µA]
Behaviour with overload
Overload protection, short-circuit protection of the outputs
Digital inputs on pin 2 with type A ports
Number of inputs
Connection type
Connection technology
Nominal input voltage [V]
Nominal input current [mA]
Sensor current [mA]
Total current consumption [A]
Input voltage range "0" signal [V]
Input voltage range "1" signal [V]
Input filter time [µs]
Overload protection, short-circuit protection of sensor supply
Potential isolation/isolation of the voltage ranges
24 V supply (communications power and sensor supply, IO-Link
ports)/bus connection (Ethernet 1) [V]
24 V supply (communications power and sensor supply, IO-Link
ports)/bus connection (Ethernet 2) [V]
24 V supply (communications power and sensor supply, IO-Link
ports)/FE
Bus connection (Ethernet 1) / FE [V]
Bus connection (Ethernet 2) / FE [V]
Bus connection (Ethernet 1) / bus connection (Ethernet 2) [V]
IO-Link Master EtherCat
200
16
12 (48 Ω; with nominal voltage)
12
(1.2 H; 12 Ω; with nominal voltage)
Max 150 (at power on)
Max 200 (at power off)
max 5500 per second
(with load current)
max 1 per second
(with inductive nominal load)
-15 DC
max 1
max 300
Switching off with automatic restart
electronic
4 (EN 61131-2 type 1)
M12 connector, X01  X04 double
occupancy
2 / 3 wire
24 DC
typ 3
Max 200 for each channel from
L+/L-
Max 16 from L+/L-
-35 DC
1530 DC
< 1000
electronic
Test voltage
500 AC, 50 Hz, 1 min
500 AC, 50 Hz, 1 min
500 AC, 50 Hz, 1 min
500 AC, 50 Hz, 1 min
500 AC, 50 Hz, 1 min
500 AC, 50 Hz, 1 min
UK