Assembling The Panel - Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual

2.6 Assembling the Panel

With the back box secured to the wall and all external
cabling ready for termination, assemble the panel as
follows:
1 Ensure that all power to the panel is isolated and
observe ALL safety and anti-static precautions when
installing the PCB assembly.
2 Install all kits that require the removal of the PCB
assembly.
3 Align the PCB assembly to the supporting pillars and,
using a No. 1 Posidriv screwdriver, screw the eight
(8) M3 x 8mm SEM screws into position.
4 Fit the labels. They may require the application of a
low tack adhesive:
i
Apply low tack adhesive to hatched area indicated.
ii Slide each label into position.
iii Apply slight pressure to the area along the bottom
edge of the fascia to ensure the labels are secure.
5 Apply the mains power supply and then connect the
batteries. Check the PCB assembly operates correctly
and then isolate all power to the panel.
6 At the PCB assembly:
i
Noting the cable polarity, connect all cables and
secure at the correct termination blocks, see
Cables & Wiring.
ii Set all required hardware jumper configurations,
refer to the Section 4 Commissioning.
7 Fit the RS485 Interface Module PCB, if applicable,
refer to Section 2.7.1 Fitting the RS485 Interface
Module PCB.
8 Re-apply the mains power supply and then connect
the batteries.
9 Disconnect the links at the earth fault monitoring
jumper, J19, and configuration lock, J9. Then connect
the RS232 9-way 'D' type Data Transfer Lead
(PN 082-173) to the panel at the RS232 connector,
PL5. Using the Support Tool, transmit the latest system
configuration to the panel.
10 Remove the lead and fit the links at J9 and J19, then
fit the cover.
Note: Connect the earth wire to the inner side wall of the
cover at the tag marked with the earth symbol.
Cables & Wiring
i
Power Supply from transformer (TB1),
ii
CFG Outputs D and C (TB3),
iii
24 V Auxiliary Power Supply (TB4),
iv
Sounder Outputs B and A (TB4),
v
Loop Cable Output (TB5),
vi
RS485 Communications Cable (TB6),
vii
FBF Communications Cable (VdS Only) (TB10),
viii
FBF Power Supply (VdS Only) (TB9),
ix
Digital / ÜE Cable (TB8), and
x
Switchable -VE Outputs (TB2),
xi
Keyswitch (PL7).