Rs485 Communications Link - Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
ZONE FIRE
ZONE FIRE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
ZONE FAULT
ZONE FAULT
DISABLE/TEST
DISABLE/TEST
FIRE
ID50 FIRE CONTROL PANEL
Complies with EN54-2/4 1997
Period of Manufacture 1999
DISABLEMENT
TEST
POWER SUPPLY FAULT
DELAYS ACTIVE
EARTH FAULT
FIRE OUTPUT: FAULT / DISABLED
SYSTEM FAULT
FIRE OUTPUT ACTIVE
SOUNDER: FAULT / DISABLED
PLANT ALARM
PRE- ALARM
POWER
FIRE CONTROL O/P: FAULT / DISABLED
B A
B A
TB6
TB6
TB6
TB6
RS485
Intermediate
If Fitted As First
Station On RS485
Comms Link
997-263-000-11, Issue 11
January 2010

2.7 RS485 Communications Link

The panel is capable of communicating with a maximum
of sixteen (16) repeaters (active IDR-2A or passive
IDR-2P) or mimic panels (IDR-M) (for further details
concerning the repeaters refer to 997-411, IDR-2A, -2P
& -6A Repeaters User Manual or 997-412, IDR Mimic
Installation and Commissioning Manual). The panel
is connected to the repeaters in a 'daisy-chain'
arrangement via the RS485 Communications terminal
block, TB6, on the PCB assembly. The panel must be
fitted with the RS485 Interface Module PCB at connector
PL3 on the PCB assembly (see Section 2.7.1, Fitting
the RS485 Interface Module PCB).
The two end stations require a termination resistor to be
fitted as illustrated below.
To connect a panel to an RS485 communications link:
1 Ensure the following:
2 Fit the RS485 Interface Module PCB as described in
3 Connect the RS485 communications cable to the
7
8
9
4
5
6
[
1
2
3
Note: If connecting the panel at either end of the RS485
4
0..9
0
MUTE BUZZER
FAULT
EXTEND DELAY
END DELAY/
EVACUATE
SILENCE/
RESOUND
RESET
4 Using the configuration procedure - refer to
B A
B A
B A
TB6
RS485
RS485
If Fitted As Last
Station(s)
Station On RS485
Comms Link
16
i
All power to the panel is isolated.
ii Access to the panel electronics is possible.
ii The interlink wire is disconnected at the batteries.
the instructions in Section 2.7.1, Fitting the RS485
Interface Module PCB).
RS485 Communications terminal block, TB6, refer
to Section 4.4.2, RS485 Communications Link.
communications link, connect a 150R termination
resistor (supplied separately) as shown below.
Section 5.5.4.6, Number of Repeaters, configure the
panel and RS485 communications link.
B A